IOM Instructions
Unit Start-Up Procedure
Figure 23: Test Mode Pins
UNIT OPERATING CONDITIONS
Table 7: HB Coax Water Pressure Drop
U.S.
Model
l/s
GPM
0.75
0.05
006
1.1
0.07
1.5
0.09
1.1
0.07
009
1.8
0.11
2.3
0.14
1.5
0.09
012
2.3
0.15
3.0
0.19
1.9
0.12
015
2.8
0.18
3.8
0.24
2.3
0.14
018
3.4
0.21
4.5
0.28
3.0
0.19
024
4.5
0.28
6.0
0.38
3.8
0.24
030
5.6
0.35
7.5
0.47
4.5
0.28
036
6.8
0.43
9.0
0.57
5.3
0.33
042
7.9
0.50
10.5
0.66
6.0
.038
048
9.0
0.57
12.0
0.76
7.5
0.47
060
11.3
0.71
15.0
0.95
Short test pins together to
enter Test Mode and speed-
up timing and delays for 20
minutes.
Pressure Drop, psi [kPa]*
30°F [-1°C]
50°F [10°C]
0.5 (3.7)
0.3 (2.3)
0.8 (5.3)
0.5 (3.5)
1.3 (8.8)
0.9 (6.1)
1.3 (9.0)
0.6 (4.4)
2.1 (14.1)
1.4 (9.4)
3.5 (24.3)
2.6 (17.9)
1.9 (12.8)
1.1 (7.6)
3.6 (25.0)
2.6 (17.8)
6.7 (46.1)
5.0 (34.3)
1.0 (6.9)
0.6 (4.4)
1.8 (12.4)
1.4 (9.3)
3.3 (22.7)
2.5 (17.5)
2.1 (14.5)
1.4 (9.9)
3.4 (23.4)
2.6 (17.6)
5.9 (40.6)
4.6 (31.5)
2.2 (15.2)
1.7 (11.6)
4.0 (27.6)
3.2 (22.2)
7.2 (49.6)
5.9 (40.6)
1.3 (9.0)
0.9 (6.1)
2.3 (15.8)
1.8 (12.5)
4.2 (28.9)
3.4 (23.2)
1.8 (12.4)
1.4 (9.6)
3.1 (21.4)
2.4 (16.8)
5.4 (37.2)
4.4 (30.0)
2.3 (15.8)
1.8 (12.1)
4.3 (29.6)
3.5 (24.2)
7.9 (54.4)
6.5 (44.8)
1.8 (12.4)
1.5 (10.1)
3.4 (23.4)
3.0 (20.4)
6.2 (42.7)
5.5 (37.9)
3.4 (23.4)
2.8 (19.2)
6.8 (46.9)
5.9 (40.8)
12.6 (86.8)
11.1 (76.8)
HBH/V CompaCt
WARNING! When the disconnect switch is closed, high
voltage is present in some areas of the electrical panel.
Exercise caution when working with energized equipment.
CAUTION! Verify that ALL water control valves are open and
allow water flow prior to engaging the compressor. Freezing
of the coax or water lines can permanently damage the heat
pump.
70°F [21°C]
0.2 (1.6)
0.4 (2.7)
0.7 (4.8)
0.4 (2.8)
1.1 (7.4)
2.1 (14.7)
0.8 (5.3)
2.1 (14.3)
4.1 (28.3)
0.5 (3.4)
1.1 (7.6)
2.1 (14.7)
1.1 (7.6)
2.1 (14.7)
3.9 (26.9)
1.4 (9.6)
2.8 (19.3)
5.2 (35.8)
0.7 (4.8)
1.5 (10.3)
2.9 (20)
1.2 (8.3)
2.1 (14.7)
3.8 (26.2)
1.5 (10.3)
3.1 (26.4)
5.7 (39.3)
1.3 (9.0)
2.7 (18.6)
5.1 (35.1)
2.4 (16.5)
5.4 (37.2)
10.3 (71.0)
Heat Controller, Inc.
WARNING!
CAUTION!
*Note: To convert
kPa to millibars,
90°F [32°C]
multiply by 10.
0.2 (1.6)
0.3 (2.2)
0.6 (4.0)
0.3 (1.9)
0.9 (6.2)
1.8 (12.7)
0.6 (4.1)
1.8 (12.1)
3.6 (24.5)
0.4 (2.8)
1.0 (6.9)
1.9 (13.1)
0.9 (6.2)
1.8 (12.4)
3.4 (23.4)
1.2 (8.3)
2.5 (17.2)
4.7 (32.4)
0.6 (4.1)
1.4 (9.6)
2.6 (17.9)
1.0 (6.9)
1.9 (13.1)
3.4 (23.4)
1.3 (9.0)
2.8 (19.3)
5.2 (35.8)
1.2 (8.3)
2.6 (17.9)
4.8 (35.1)
2.2 (15.2)
5.0 (34.5)
9.6 (66.1)