8.7

Electrical connections

Danger!
Supply voltage!
The connection to the electric mains should only be carried out by qualified skilled personnel and must
correspond to the legal provisions in force in your region.
Prior to connecting the device, please check the name plate to avoid exceeding the indicated values. The voltage
tolerance is +/- 10%.
The installer is responsible for supplying and installing the power cable. Be sure to provide the proper fuses or
breakers based on the data information located on the nameplate.
RA 1080-2200
The mains socket must be provided with a magnetothermal
differential circuit breaker (In=0.03A) which is adjusted on
the basis of the dryer's consumption (see nominal values
on the name plate of the dryer). The cross-section of the
power supply cables must correspond to the consumption
of the dryer. In this respect, the ambient temperature, the
cable laying conditions, the length of the cables and the
requirements of the local electricity supplier need to be
considered.
CAUTION!
Please observe the direction of rotation of the compressor!
In this system, the direction of rotation of the compressor is supervised by a reverse-phase
protector (RPP).
When this guard is triggered, the DMC24 goes into alarm mode (the alarm LED flashes
display of the DMC24 shows
direction of rotation must be changed by interchanging two phases. These modifications must only be
carried out by a qualified electrician.
Do not by-pass the RPP protector:
rotation, the compressor will fail immediately. This will void the guarantee.
DRYPOINT® RA 1080-8800
and
). In the event that the compressor does not run, the
If the device is operated with the incorrect direction of
RA 2400-8800
L1
L2
L3
QS
Installation
PE
and the
19