4 Operation
To adjust/overrule the leaving water temperature (main)(NOT
linked to room thermostat control)
INFORMATION
Adjusting  the  leaving  water  temperature  is  permanent
unless  the  leaving  water  temperature  is  according  to  a
schedule. In that case the overruling is valid until the next
scheduled action.
1 Go to [7.4.2]: 
 > User settings > Preset values > LWT main.
2 Press 
 or 
 to adjust/overrule. Example:  
To adjust the leaving water temperature (additional)
1 Go  to  the  additional  leaving  water  temperature  home  page
(LWT add).
2 Press 
 or 
 to adjust. Example:  
4.5
Domestic hot water control
4.5.1
About domestic hot water control
Depending  on  the  DHW  tank  mode  (installer  setting),  you  use  a
different domestic hot water control:
▪ Reheat mode
▪ Scheduled mode
▪ Scheduled + reheat mode
CAUTION
The backup heater permission schedule is used to restrict
or  allow  backup  heater  operation  based  on  a  weekly
program.  Advice:  In  order  to  avoid  unsuccessful
disinfection  function,  at  least  allow  the  backup  heater  (by
the weekly program) for minimum 4 hours starting from the
scheduled  start­up  of  disinfection.  If  the  backup  heater  is
restricted  during  disinfection,  this  function  will  NOT  be
successful  and  the  applicable  warning  AH  will  be
generated.
INFORMATION
In  case  of  error  code  AH  and  no  interruption  of  the
disinfection  function  occurred  due  to  domestic  hot  water
tapping, following actions are recommended:
▪ When  the  Domestic  hot  water  >  Type  >  Reheat  or
Reheat  +  sched.  is  selected,  it  is  recommended  to
program the start­up of the disinfection function at least
4  hours  later  than  the  last  expected  large  hot  water
tapping.  This  start­up  can  be  set  by  installer  settings
(disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is  selected,  it  is  recommended  to  program  a  Storage
eco  3  hours  before  the  scheduled  start­up  of  the
disinfection function to preheat the tank.
To determine which DHW tank mode you are using (method 1)
Check the installer settings table filled in by the installer.
User reference guide
10
35°C 37°C
45°C 47°C
To determine which DHW tank mode you are using (method 2)
Prerequisite: User profile = Detailed.
1 Go to the DHW tank temperature home page (Tank).
2 Check which icons are displayed:
If... is displayed
Reheat mode
Scheduled mode
Scheduled + reheat mode
 
4.5.2
Reheat mode
In  reheat  mode  ( ),  the  DHW  tank  continuously  heats  up  to  the
desired temperature (example: 50°C).
T t
1
60°C
50°C
40°C
15°C
00:00
07:00
▪ T
: DHW tank temperature
t
▪ t: Time
In reheat mode, you can do the following:
You can...
Read out the desired reheat temperature.
Adjust the reheat temperature.
Condition:   is displayed on the DHW tank
temperature home page.
Activate the DHW tank booster mode.
(Only for field supplied domestic hot water
pump for secondary return)
Program a domestic hot water pump schedule
to determine when to turn ON and OFF the pump.
When turned ON, the pump runs and makes sure
hot water is instantly available at the tap. To save
energy, only turn ON the pump during periods of
the day when instant hot water is necessary.
See also:
"4.5.5 Using the DHW tank temperature home page" on page 11
"4.5.6 Using the DHW tank booster mode" on page 12
"4.7 Preset values and schedules" on page 15
Then the DHW tank mode =...
3
2
4
14:00
21:00
t
Location
DHW tank
temperature
home page
Menu structure
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351749­1 – 2013.06