5
|
Operation
5.7 Domestic hot water control
5.7.1 About domestic hot water control
User reference guide
30
2 Adjust the desired leaving water temperature.
a
2
35
°C
Main zone
a
3
45
°C
Additional zone
a Actual leaving water temperature
b Desired leaving water temperature
If scheduling is on after changing the desired leaving water temperature
▪
The temperature will stay the same as long as there is no scheduled action.
▪
The desired leaving water temperature will return to its scheduled value
whenever a scheduled action occurs.
You can avoid scheduled behaviour by (temporarily) turning off scheduling.
To turn off leaving water temperature scheduling
1 Go to one of the following:
▪
[2.1]: Main zone > Schedule
▪
[3.1]: Additional zone > Schedule
2 Select No.
To enable weather-dependent operation for the leaving water temperature
See
"5.9.4 Using weather-dependent
Depending on the DHW tank mode (installer setting), you use a different domestic
hot water control:
▪
Reheat only
▪
Schedule + reheat
▪
Schedule only
CAUTION
The booster heater permission schedule is used to restrict or allow booster heater
operation based on a weekly program. Advice: In order to avoid unsuccessful
disinfection function, at least allow the booster heater (by the weekly program) for
minimum 4 hours starting from the scheduled start-up of disinfection. If the booster
heater is restricted during disinfection, this function will NOT be successful and the
applicable warning AH will be generated.
b
+
–
b
+
–
4
curves" [
47].
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685231-1 – 2022.04