Terminal Outlet Positions - Worcester 440CDi Instruction Manual

Floor standing rsf gas-fired condensing combination boiler
Table of Contents

Advertisement

0mm
DORMER
WINDOW
ELUX WINDOW
2000mm below a Velux window,
600mm above or to either side
of the Velux window
RAINPIPE
300mm
mm
1500mm
Window
300mm
300mm above,
below and either
side of an opening
door, air vent or
opening window
1500mm between a vertical flue
terminal and a window
or dormer window
1500mm
400mm
400mm from a pitched roof
or in regions with heavy
snow fall 500mm
1200mm between terminals
facing each other
NOTE: All measurements are the minimum
INSTALLATION & SERVICING INSTRUCTIONS
8 716 115 219b (09.2008)
The flue cannot be
lower than 1000mm
from the top of a light
well due to the build up
of combustion products
1200mm
300mm to an
internal or
external corner
clearances required. Terminals must
be positioned so to avoid combustion
products entering the building
Flue clearances must be at least 300mm
from the ground. Terminal guards must be
fitted if the flue is less than 2 metres from
the ground or if a person could come into
contact with the flue terminal.

TERMINAL OUTLET POSITIONS

NOTES:
Plume management kits are available for
100mm horizontally terminated flues.
Please refer to the installation instructions
supplied with the plume management kits.
If plume redirection is utilised, the
clearance from any opening must
be increased in the direction of the
plume to 1500mm.
Opening
in building
Min.
1500 mm
Direction of
flue discharge
Plume deflector
300mm
300mm
Clearance no less than
200mm from the lowest point
of the balcony or overhang
NOTE:
Installations in carports
are not recommended
1,200mm from an opening on the
same wall (ie: door or window
leading into a dwelling) in a carport
with both sides open, to prevent the
300mm
build up of combustion products.
TERMINAL OUTLET POSITIONS
17