FIGURE 26
TYPICAL GAS VALVE
INLET
PRESSURE TAP
TABLE 5
LP GAS PIPE CAPACITY TABLE (CU. FT./HR.)
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column inlet pressure).
(Based on a Pressure Drop of 0.5 Inch Water Column)
Nominal
Iron Pipe
Size, Inches
10
20
30
1/2
275
189
152
3/4
567
393
315
1
1,071
732
590
1-1/4
2,205
1,496
1,212 1,039
1-1/2
3,307
2,299
1,858 1,559
2
6,221
4,331
3,465 2,992
Example (LP): Input BTU requirement of unit, 120,000
Equivalent length of pipe, 60 ft. = 3/4" IPS required.
FIGURE 27
TYPICAL MANIFOLD PRESSURE READING
Length of Pipe, Feet
40
50
60
70
80
129
114
103
96
89
267
237
217
196
182
504
448
409
378
346
913
834
771
724
1,417
1,275
1,181
1,086 1,023
2,646
2,394
2,205
2,047 1,921
HIGH FIRE
MANIFOLD
PRESSURE
ADJUSTMENT
LOW FIRE
PRESSURE
MANIFOLD
ADJUSTMENT
OUTLET
PRESSURE
TAP
90
100
125
150
83
78
69
63
173
162
146
132
322
307
275
252
677
630
567
511
976
866
787
1,811 1,606
1,496
9. Note or adjust the manifold
pressure to give:
A. 1.7" w.c. for natural gas low
fire.
B. 4.8" w.c. for LP gas low fire.
10. To adjust the pressure regulator
for low fire, remove the regulator
cap on the top of the regulator.
See Figure 27.
11. Turn the adjustment screw
clockwise to increase pressure or
counterclockwise to decrease
pressure.
12. Securely replace the regulator
cap for low fire.
13. Verify pressures for high and low
fire operation.
14. Shut off gas at the manual gas
valve and remove the U-Tube
manometer.
15. Replace the manifold pressure
tap plug before turning on gas.
Check for leak.