Figure 28. Supply valve connection fittings.
Leak test:
1. Mix a 50-50 solution of water and dish
soap.
2. Light appliance- see lighting instructions
on the inside back cover of this manual
or on the stove's rating plate.
3. Brush or spray all joints and connections
with the soapy water solution.
4. If bubbles appear at any connection or
seam or a gas odor is detected, immedi-
ately turn gas control knob to the OFF
position.
5. Tighten or reconnect the leaking joint
and retest for any gas leaks.

Gas Pressure

Correct gas pressure is essential for efficient and safe
operation of the GF 300 DV gas stove. It is important
that the correct pressure is established at the time of
the installation. Proper gas pressure provides a
consistent flow of gas to the appliance and is instru-
mental in checking for gas leaks.
Pressure Test: Attach a manometer to the appro-
priate test point on the valve. See fig. 29. The gauge
connections are located on the front of the valve
under the On/Off/Pilot- knob. Gauge connections are
identified by:
E - for Inlet or Supply Pressure (the amount of
gas coming to the valve.)
A - for Manifold Pressure (the amount of gas that
is coming out of the valve to the burner.)
ALWAYS TEST PRESSURES WITH VALVE CONTROL
KNOB SET ON HIGH.
E
A
Figure 29. Pressure test points.
INLET GAS PRESSURES
(inches water column)
NATURAL GAS
PROPANE
The appliance and its appliance main gas valve
must be disconnected from the gas supply piping
system during any pressure testing on that system
at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas
supply line by closing its individual manual gas
shut-off valve (gas cock) during any pressure
testing of the gas supply piping system that is
equal to or exceeds pressures of 1/2 psig (3.5 kPa).
MANIFOLD PRESSURES
(inches water column)
NATURAL GAS
PROPANE

High Altitude Adjustment

Installations located at altitudes from 2000 - 4500 ft.
(610 m -1370 m) DO NOT require adjustment for alti-
tude. DO NOT DERATE THIS APPLIANCE FOR ALTITUDE.
MIN
MAX
5.0
7.0
12.0
14.9
MIN
MAX
1.2
3.8
2.9
11.0
19