Direct vent gas heater

Advertisement

Jøtul GF3 DVII
Allagash
Direct Vent
Gas Heater
Installation
and
Operation
Instructions

Advertisement

Table of Contents
loading

Summary of Contents for Jøtul Allagash GF3 DVII

  • Page 1 Jøtul GF3 DVII Allagash Direct Vent Gas Heater Installation Operation Instructions...
  • Page 2 Welcome to Jøtul... Congratulations on the purchase of your new Jøtul GF3 DVII Allagash gas stove. We at Jøtul are happy you’ve made the decision to warm your hearth with a Jøtul product. Your new Allagash incorporates our experience as the world’s largest manufacturer of solid fuel burning appliances for over 150 years.
  • Page 3: Table Of Contents

    Jøtul GF3 DVII Allagash Table of Contents Direct Vent Gas Heater Manufactured and Distributed by: Standards..........3 Jøtul A.S.A. General Information ......3 Fredrikstad, Norway Safety Information ......4 Jøtul North America Portland, Maine Location ..........4 Hearth Requirements...... 4 Test Standards Stove Clearances....... 5 Warnock Hersey Mantel and Trim .......5 This appliance complies with...
  • Page 4: Specifications

    Specifications The Jøtul GF3 DVII Allagash is a Direct Vent wall furnace and is designed as a sealed combustion, air circulating gas appliance for residential applications. The following vent components are approved for use 28” with the Jøtul GF3 DVII, vented directly to the 711 mm outside of the house: •...
  • Page 5: Standards

    Standards established in the National Fuel Code, ANSI This appliance complies with National Safety stan- Z223.1.(NFPA 54). In Canada, the codes have been dards and is tested and listed by Intertek Testing established in CAN/CGA B149 Fuel Installation Services of Middleton, WI Code.
  • Page 6: Safety Information

    Safety Information Location This appliance will reach high surface temperatures In selecting a location for the stove, consider the during normal operation. Please read the following following points: notes to help ensure safe operation. 1) Heat distribution 2) Vent termination requirements •...
  • Page 7: Stove Clearances

    Clearance Requirements Minimum clearances for the GF3 DVII Parallel Installation Allagash 4” Rear: 4” / 102 mm 102 mm Ceiling: 12” / 305 mm Corner: 4” / 102 mm Right Side: 4” / 102 mm Left Side: 10” / 254 mm (required for complete access of the lighting instructions) Right Left Side...
  • Page 8: Venting Requirements

    Venting Requirements Horizontal Overhang 2 ft. 2 ft. min. There are two types of venting configurations min. approved for use with the Allagash gas stove - Lowest Horizontal Termination and Vertical Termination. Discharge Termination Opening The GF3 DVII Allagash is approved for use with 2 ft.
  • Page 9: Horizontal Venting

    Restrictor Sliders First Restriction Horizontal Length Setting - install Wall 12” Max. screw into the Thimble Wall Plate OUTER hole of #940B #942B 1 2 1 2 sliders. Second Restriction 90° Elbow Setting - screw #990B installed into MIDDLE hole of 24”...
  • Page 10: Co-Linear Hearthmount

    Co-linear Vent Installation A DIRECT VENT TERMINATION KIT AND CAP IS The GF 3 DV Allagash may be vented through a REQUIRED TO masonry or Class A prefabricated chimney using a ALLOW FRESH AIR Co-linear Flexible Vent system approved for use with INTO THE CHIMNEY.
  • Page 11: Mobile Home Installation

    Simpson Dura-Vent Chimney Vertical Termination Cap #991 Conversion Kit (Not included in kit). The GF3 DVII Allagash is approved for use with Simpson Dura-Vent Simpson Dura-vent Chimney Kit as shown in Figure Termination Kit 9. These installation requirements must be followed: GF 3 DV ALLAGASH 1.
  • Page 12: Vent Window

    Max. 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 Vent Termination Window 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0...
  • Page 13: Vent Terminal Clearances

    Vent Terminal Clearances Figure 10. Vent Terminal Clearances - National Fuel Gas Code. A = Clearance above grade, veranda, porch , deck, or G = Clearance to inside corner: 6 inches (16 cm) min. balcony : *12 inches (30 cm) minimum. Jøtul N.A.
  • Page 14: Fuel Conversion

    Fuel Conversion The Allagash gas stove is shipped from the factory IN CANADA: THE CONVERSION SHALL BE CARRIED equipped as a NATURAL GAS unit; However, the OUT IN ACCORDANCE WITH THE REQUIREMENTS OF stove is shipped with the necessary gas conversion THE PROVINCIAL AUTHORITIES HAVING JURISDIC- kit to convert the stove to burn propane gas.
  • Page 15 Screws Replace with the appropriate pilot orifice. #51 for natural gas Regulator Tower #30 for propane Be certain the orifice is securely tightened. Replace the Pilot Hood into the base. 12. Replace the Variable Regulator: Using a Torx T- 20 screwdriver, remove the three specialty screws from the front of the valve regulator.
  • Page 16: Gas Connection

    Gas Connection Secure all joints tightly using appropriate tools and sealing compounds (for propane units be sure to use compounds that are propane resistant). Turn on NOTE: IF THE OPTIONAL BLOWER KIT (# 129161) IS gas supply and test for gas leaks using a soapy water TO BE INSTALLED ON THE STOVE AT THE TIME OF THE solution.
  • Page 17: High Altitude Adjustment

    ALWAYS TEST PRESSURES WITH VALVE CONTROL High Altitude Orifice Chart KNOB SET ON HIGH. Orifice The appliance must be isolated from the gas Elevation Fuel Part No. Size supply line by closing its individual manual gas Natural Gas 129130 0 - 2000 ft. shutoff valve (gas cock) during any pressure testing Propane 1.5 mm...
  • Page 18: Air Shutter Settings

    Air Shutter & Flame Picture Log Set Installation Adjustment The Allagash is equipped a one piece log set and is The GF3 DVII Allagash is shipped from the packaged in bubble wrap inside the firebox. The log factory equipped to use NATURAL GAS. If the stove is set must be removed from the packaging and converted to use Propane, it will be necessary to arranged in the unit prior to start up of the gas...
  • Page 19: Optional Blower Installation

    Optional Blower Installation IMPORTANT: IF THE OPTIONAL FORCED BLOWER KIT(PART # 129161) IS TO BE INSTALLED ON THE STOVE AT THE TIME OF THE INSTALLATION Blower OR IN THE FUTURE, THE GAS SUPPLY LINE SHOULD BE INSTALLED AS CLOSE TO THE FLOOR AS POSSIBLE. Gas Line USE OF A 90°...
  • Page 20: Remote Control / Thermostat

    Snapstat CAUTION: (attached to blower bracket) LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING BLOWER THE CONTROLS. WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. ALWAYS VERIFY PROPER OPERATION AFTER SERVICING THE APPLIANCE. HI/LO SWITCH Plug Wire Harness Figure 22. Attaching the blower wire harness. THERMOPILE ROCKER SWITCH...
  • Page 21: System Check

    System Check 1. PURGE THE GAS LINE: When lighting the appli- ance for the first time it will take a few moments to CAUTION: DO NOT ATTEMPT TO ALTER THE clear the gas line of air. Once this purge is complete, FLAME APPEARANCE BY POSITIONING THE the appliance will operate as described in the GAS VALVE IN ANY OTHER POSITION...
  • Page 22: Operation Instructions

    Operation Maintenance 1. The Allagash is equipped with an On/Off/T-stat The Allagash Direct Vent gas stove and its venting rocker switch or can be controlled using an system should be inspected before use and at least optional wall mounted thermostat. A separate annually by a qualified service technician.
  • Page 23 With proper care and maintenance, your appli- ance will provide you with years of enjoyment. If you SERVICE LOG: experience any problem or inconsistency with your Second Year Jøtul Allagash gas stove, contact your authorized Jøtul dealer for assistance. To expedite the proper service for your appliance Service Technician____________________ the following information will help your dealer determine what you will need for parts and service.
  • Page 24: Illustrated Parts List

    Illustrated Parts List...
  • Page 25 Jøtul GF3 DVII Allagash Parts Door Pins..........125960 Gasket pilot assembly ......129116 Glass Latch ..........129135 Valve Bracket ..........129105 Glass Frame ........12911292 Gasket Ignition Door ......129117 Glass Panel ..........129113 Wiring Harness complete.....154319 Glass Gasket (7/16 tadpole) ....129124 Door Clip ...........122009 Glass Panel w/ gasket ......
  • Page 27: Lighting Instructions

    LIGHTING INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTING. WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE. • If your gas supplier cannot be reached, call the A.
  • Page 28 This appliance must be installed in conformance with local and national building regulations. Before beginning the installation, it is important that the these instructions be carefully read and understood. Jøtul pursues a policy of continual product development. Consequently, products may differ in specification, color or type of accessories from those illustrated or described in various publications.