Venting Through a Fireplace
Co-linear Vent Installation
This appliance may be vented through a masonry or
Class A prefabricated chimney using a Co-linear Flexible
Vent system approved for use with a solid-fuel burning
fireplace. When installed in the manner described below,
this system can improve the performance of the appli-
ance in cold climate situations, as well as simplify the
vent installation. See fig. 9.
These installation requirements must be followed:
1. Prior to the installation the chimney flue must be
thoroughly cleaned and inspected by a qualified
chimney service person.
2. In a masonry chimney, a fireclay liner must be present
the entire length of the chimney.
3. Prefabricated chimneys must be UL 103 or ULC S-629
listed and have a minimum INSIDE diameter of 6
inches, (150 mm).
4. No appliance can be installed into a chimney flue
serving any other appliance of any kind.
5. THE AIR INTAKE FLEX PIPE MUST EXTEND BEYOND THE
DAMPER AREA OF THE FIREPLACE. If the intake flex
duct does not extend the full length of the chimney
and connect to both the unit and the termination
cap, A METAL BLOCK OFF PLATE MUST BE CON-
STRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO
THE END OF THE INTAKE FLEX AND MUST COM-
PLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM.
Consult with the local code authority having juris-
diction before proceeding with this type of installation.
Refer to the vent manufacturer's instructions for
specific installation requirements.
WARNING: FAILURE TO POSITION THE PARTS AND
STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE, MAY RESULT IN PROP-
ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES
AS DEFINED IN THIS MANUAL AND IN THE INSTRUC-
TIONS PROVIDED WITH EACH VENT COMPONENT.
Exhaust Gas
Max.
Co-linear
Height 15 ft.
(10.66 m)
Min.
Co-linear
Height 8
ft.
(2.44 m)
Air Intake Flex
pipe must
extend above
the damper.
Figure 9.
Co-linear Adaptor installed through a masonry chimney.
Figure 10. Simpson Dura-Vent #923GCL Co-linear Adaptor.
GF 100 DV II:
A : 16 3/4"
GF 200 DV II:
A : 18"
Add 2 1/4" with Long Legs.
Subtract 1" with Plinth
GF 100 DV II Nordic QT
GF 200 DV II Lillehammer
High Wind
Cap
Intake Air
Sealed
Damper
Max.
Offset 24"
(609 mm)
B : 20 3/4"
B : 22"
11