17 Troubleshooting Guide

17.1. Self Diagnosis Function (CU-2E15LBE and CU-2E18LBE)
Abnormality or protection control
Diagnosis
display
H11
Indoor/outdoor abnormal
communication
H12
Indoor unit capacity unmatched
H14
Intake air temperature unmatched
H16
Outdoor current transformer
H19
Indoor fan motor mechanism lock
H23
Indoor heat exchanger temperature
sensor
H27
Outdoor air temperature sensor
H28
Outdoor heat exchanger temperature
sensor 1
H30
Outdoor discharge pipe temperature
sensor
H32
Outdoor heat exchanger temperature
sensor 2 (discharge pipe temp)
H34
Outdoor heatsink temperature sensor at
Control Board
H36
Outdoor gas pipe temperature sensor
H37
Outdoor liquid pipe temperature sensor Continue for 2 sec
H39
Abnormal indoor operating unit or
standby units
H41
Abnormal wiring or piping connection
H97
Outdoor fan motor mechanism lock
H98
Indoor high pressure protection
H99
Indoor heat exchanger freeze
protection
F11
Cooling/heating cycle changeover
abnormality
F17
Indoor standby unit freezing
F90
PFC circuit protection
F91
Refrigeration cycle abnormality
Abnormality
judgement
> 1 min after starting
Indoor fan operation can
operation
start by entering into force
cooling operation
Continue for 5 sec
Continue for 5 sec
Continue for 5 sec
Continue for 5 sec
Continue for 5 sec
Continue for 2 sec
Continue for 2 sec
4 times occurrences
within 30 minutes
2 times occurrences
within 20 minutes
58
Emergency
Primary location to verify
operation
• Internal/external cable
connections
• Indoor/outdoor PCB
• Indoor unit total capacity
• Intake air temperature sensor
(defective or disconnected)
• Decreased amount of refrigerant
• Outdoor PCB
• Fan motor
• Indoor PCB
• Heat exchanger temperature
sensor
(defective or disconnected)
• Outdoor air temperature sensor
(defective or disconnected)
• Outdoor heat exchanger
temperature sensor
(defective or disconnected)
• Outdoor discharge pipe
temperature sensor
(defective or disconnected)
• Outdoor heat exchanger
temperature sensor
(defective or disconnected)
• Outdoor heatsink temperature
sensor at control board
(defective or disconnected)
• Outdoor gas pipe temperature
sensor
(defective or disconnected)
• Outdoor liquid pipe temperature
sensor
(defective or disconnected)
• Piping connection error
• Indoor/outdoor connection cable
connection error
• Wiring or piping connection
• Outdoor fan motor
• Air filter dirty
• Air circulation short circuit
• Insufficient refrigerant
• Air filter dirty
• 4-way valve
• V-coil
• Outdoor expansion valve leakage
• Indoor unit pipe temperature
sensor
• Outdoor PCB
• Outdoor fan motor
• No refrigerant (3-way valve is
closed)