Plume Kit Installation Instructions - Viessmann VITODENS 200-W Installation Instructions Manual

4.8 to 35.0 kw wall mounted gas fired condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Vitoden 200-W installation

Plume kit installation instructions

The plume kit enables the relocation of the flue outlet of a standard horizontal flue system
to another position and is available as an optional extra, please contact your supplier for
further information.
Routing options
A
Plume kit standard delivery 2m max
length
Ensure the max. length of the entire
balanced flue system is not exceeded.
The max. length is reduced by 1m when
using a further 87° bend or 2 x 45° bends.
4/9/07
7:27 pm
Page 19
B
C
Deduct 3m from the max. possible
standard concentric horizontal flue length
and add the standard plume kit max length
to give max. length of entire flue system.
ie. 6m - 3m +2m = 5m max.
Plume kit standard delivery
additional options:
• 2 x 87º bends
• 1 pipe 1m long
Plume kit standard delivery
additional options:
• 2 x 45º bends
• 1 pipe 1m long
19