Refrigeration System; Note: Thermostatic Expansion Valve No Adjustment; Lbs. Discharge Pressure; Water Temperature - Cornelius 500-Series Installation And Service Manual

Continuous flow icemaker
Table of Contents

Advertisement

WCC 500
40_
65_
162
166
50_
188
' 92
60_
214
218
70_
245
249
80_
275
279
90_
309
313
100_

REFRIGERATION SYSTEM ADJUSTMENTS

A complete understanding of the icemaker and hermetic refrigeration system is necessary before any adjust-
ments are made. The refrigeration technician must use high and low side pressure readings, water and air tem-
peratures, plus general conditions of cleanliness to assess the refrigeration system status when making any
adjustments.
All icemaker products are tested and adjusted at the factory prior to shipment where the ambient temperature
ranges from 65_ to 90_F, depending on the season of the year.
Whenever a new icemaker product is initially installed and started-up, it is imperative that the start-up operation
make the following checks and/or readjustments for local conditions.

EXPANSION VALVE

You will find a thermostatic expansion valve on icemakers, which is used to control the amount of refrigerant
flowing through the evaporator. Improperly installed or defective expansion valves may cause low production,
soft ice, squeaking from evaporator and excessive load inside evaporator.
By using general refrigeration system troubleshooting along with the pressure charts you can easily determine
whether or not the expansion valve is working properly.

ADJUSTMENT AND TROUBLESHOOTING

When troubleshooting the expansion valve you must first be sure you have adequate water flowing into evapo-
rator, a clean condenser, unit is properly ventilated, and system is properly charged and free from any restric-
tions. Also be sure compressor is operating properly.
Second, take reservoir water temperature and air temperature from condenser inlet and determine at what pres-
sure unit should be running. Machines are equipped with thermostatic valves, there is NO adjustment. If correct
pressure cannot be obtained, first be sure system has time to stabilize 10-15 minutes. Second, be sure sensing
bulb is located at 12:00 position on outlet side of evaporator about 3-4 inches away from evaporator and be sure
to insulate well and clamp tightly to tubing. If system pressures are still not adequate, take a second water and
air temperature reading and go over other parts of system for possible problems. If proper charge is question-
able evacuate and recharge to nameplate and leak check. If valve still malfunctions replace valve.
When replacing valve be sure to bleed refrigerant gas from low side port so as not to lose refrigerant oil. Use
general refrigerant system practices when replacing and recharging unit. After new valve is in place, go through
previous monitored adjustments and troubleshooting to be sure valve is functioning properly.
NOTE: Units with thermostatic expansion valve— valve is located on bottom refrigerant line. Sensing
bulb is located on top refrigerant line. On water cooled units adjust condenser modulating valve be-
fore troubleshooting expansion valve.
638085278

REFRIGERATION SYSTEM

NOTE: Thermostatic Expansion Valve NO Adjustment

– 10 lbs. Discharge Pressure

Water Temperature

WCC 700
90_
40_
65_
168
174
177
194
202
205
220
230
233
251
265
269
281
300
304
315
328
334
WCC 1000
90_
40_
65_
180
170
171
208
198
199
236
226
227
272
261
263
307
296
298
340
324
328
16
WCC 2200
90_
40_
65_
172
200
201
200
218
219
228
251
253
264
297
298
299
308
330
332
362
364
90_
203
220
254
300
332
366

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents