(2) Install the panel
a. Align the swing motor on the panel to the water
receiver of the body properly. (Refer to Fig.23)
b. Hang the four fixed rope of the main body to the
installation cover and the other three covers of
the swing motor: (Refer to Fig.23 )
CAUTIONS:
The installation cover of the swing motor must sink
into the corresponding water receiver.
c. Install the panel on the main body with bolt (M5×16)
and washer. (Refer to Fig.23)
d. Adjust the four panel hook screws to keep the panel
horizontal, and screw them up to the ceiling evenly.
e. Regulate the panel in the direction of the arrow in
Fig.11 slightly to fit the panel's center to the center
of the ceiling's opening. Guarantee that hooks of
four corners are fixed well.
f. Keep fastening the screws under the panel hooks,
.
until the thickness of the sponge between the body
.
and the panel's outlet has been reduced to about
4~6mm. The edge of the panel should contact with
the ceiling well. (Refer to Fig.24) Malfunction
described in Fig.25 can be caused by inappropriate
tightness the screw. If the gap between the panel
and ceiling still exists after fastening the screws, the
height of the indoor unit should be modified again.
You can modify the height of the indoor unit through
the openings on the panel's four corners, if the lift of
the indoor unit and the drainpipe is not influenced
(refer to Fig.26-right).
(3) Hang the air-in grid to the panel, then connect
the lead terminator of the swing motor and that
of the control box with corresponding terminators
on the body respectively.
(4) Relocate the air-in grid in the procedure of
reversed order, install the air-in grid.
(3) The installation of ventilation motor and
ventilation pipe (if necessary)
a. Using a tool to knock off the pre-punching hole.
(Refer to Fig.27)
b. Four screw hole reserved for installation.
(Refer to Fig.27 )
INSTALLATION INSTRUCTIONS
Drain side
1
Steel rope
Cover
Please operate according
to the direction of the arrow,
or it can not be disassembled
when it is necessary.
Ceiling
Panel foam2
Panel foam
Outlet air
Ceiling
Leakage
Dew
Hexagon nut
Horizontal adjust ment
Ceiling
Four screw hole
pre-punching hole
11
Drain side
2
3
3
Swing motor installation cover
4
Bolt, washer
Swing motor side
Fig.23
Body
Inlet air
Panel sealing foam
Air plate
Panel
Panel foam1
Fig.24
Fig.25
Fig.26
Fig.27