ent temperature is the approach temperature.
Approach temperature should match the values
shown in table 16. Add refrigerant to reduce approach
temperature and remove refrigerant to increase ap-
proach temperature.
TABLE 16
Model
HP21−411/413, HP21−36−230/233
HP21−511/513, HP21−48−230/233
HP21−651/653, HP21−60−230/233
FIGURE 22
OUTDOOR TEMPERATURE BELOW 60°F
(steps 6 through 8)
6− It is not recommended that the system be charged be-
low 60°F. If charging below 60°F is required, the most
reliable method is to weigh in the charge listed on the
unit nameplate. This amount (table 14) will be correct
for a system with a line set of 25 feet. If line set is longer
or shorter than 25 feet, add or remove refrigerant as
shown in table 15.
7− If ambient temperature is less than 60°F (10°C), sys-
tem should be charged using the subcooling method.
Air flow will need to be restricted to achieve pressures
in the 200−250 psig range (See figure 22.) These high-
er pressures are necessary for checking the
subcooling temperature. Block equal sections of air in-
take panels, moving obstructions sideways as shown
until liquid pressure rises above 200 psig.
8− Read liquid line pressure from gauge and convert to
condensing temperature using standard R−22 temper-
ature/pressure conversion chart (or conversion scale
on gauge.) The difference between the liquid line tem-
perature
and
the
subcooling (subcooling = conversion temperature mi-
nus
liquid
line
temperature).
temperature should approximate the values given in
table 17. Add refrigerant to increase subcooling and re-
move refrigerant to reduce subcooling.
TABLE 17
Model
HP21−410/510/650/36/48/60
Liquid Temp Minus Am-
°
bient Temp. (
F)
9 + 2
7 + 2
10 + 2
BLOCKING
OUTDOOR
COIL
OUTDOOR COIL SHOULD
BE BLOCKED ONE SIDE
AT A TIME WITH CARD−
BOARD OR PLASTIC
SHEET UNTIL PROPER
TESTING PRESSURES
ARE REACHED.
CARDBOARD OR
PLASTIC SHEET
conversion
temperature
The
subcooling
°
Subcooling
F
10 + 3
9− When unit is properly charged, liquid line pressures
should approximate those given in table 18.
D−Oil Charge
Factory oil charge in all HP21 series units is 70 fl. oz. Re-
placement oil charge is 66 fl.oz.
NORMAL OPERATING PRESSURES
OUTDOOR
COIL
ENTERING
MODE
TEMP.
COOLING
EXPANSION
VALVE
ONLY
105
HEATING
ALL UNITS
NOTE − Liquid line pressure in heating mode may vary more than +10
PSIG depending on unit matchup. All pressures are with unit operating
on high speed. Indoor return air 80°F for cooling.
V−Maintenance
At the beginning of each heating or cooling season, the
system should be cleaned as follows:
A−Heat Pump Unit
1− Clean and inspect outdoor coil. (Coil may be flushed
with a water hose.)
2− Rotate fan to check for frozen bearings or binding.
Outdoor fan motor is prelubricated and sealed with
plugs. No further lubrication is required.
3− Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4− Check all factory and field−installed wiring for loose
connections.
5− Check voltage supply at disconnect (unit not operat-
ing.) Voltage must be within range listed on unit rating
plate. If not, do not start equipment until the power
company has been consulted and the voltage condi-
is
tion corrected.
Check for correct voltage at unit (unit operating).
6− Check fan motor amp-draw.
Unit nameplate_________Actual_________.
7− Check compressor amp-draw.
Unit nameplate_________Actual_________.
NOTE − If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge checked.
Page 25
ALL UNITS
(step 9)
TABLE 18
HP21−411
HP21−511
HP21−413
HP21−513
HP21−48−233 HP21−36−230
HP21−36−230
HP21−36−233 HP21−48−230
LIQ.
SUC.
LIQ.
SUC.
AIR
+ 10
+ 5
+ 10
PSIG PSIG
PSIG PSIG
°
75
F
175
74
177
°
85
F
208
76
190
°
95
F
245
78
228
°
F
277
80
266
°
20
F
180
33
160
°
30
F
191
40
171
°
40
F
206
49
184
°
50
F
225
59
204
HP21−651
HP21−653
HP21−36−233
LIQ.
SUC.
+ 5
+ 5
+ 10
PSIG PSIG
80
182
76
84
213
79
86
242
80
88
276
82
32
175
31
40
185
38
50
206
47
62
227
57