Gas Valve; Reading Gas Pressure; Inlet Gas Pressure Range; Nominal Manifold Pressure - Johnson Controls MG9S*MP Installation Manual

Manufactured housing or modular home gas furnace 33” models – shipped in downflow configuration (95.5% afue single stage multi-position)
Table of Contents

Advertisement

420705-UIM-C-0310
ADJUSTMENT OF MANIFOLD GAS PRESSURE &
INPUT RATE
Inlet and manifold gas pressure may be measured by connecting the
"U" tube manometer to the gas valve with a piece of tubing. Follow the
appropriate section in the instructions below. Refer to Figure 33 for a
drawing of the locations of the pressure ports on the gas valve.
Turn gas off at the ball valve or gas cock on gas supply line
before the gas valve. Find the pressure ports on the gas
valve marked Out P and In P.
1.
The manifold pressure must be taken at the port marked OUT P.
2.
The gas line pressure must be taken at the port marked IN P.
3.
Using a 3/32" (2.4 mm) Allen wrench, loosen the set screw by turn-
ing it 1 turn counter clockwise. DO NOT REMOVE THE SET
SCREW FROM THE PRESSURE PORT.
Read the inlet gas pressure
Connect the positive side of the manometer to the IN P Tap on the gas
valve. Do not connect any tubing to the negative side of the manometer,
as it will reference atmospheric pressure. Refer to Figure 34 for connec-
tion details.
1.
Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.
Table 15: Inlet Gas Pressure Range

INLET GAS PRESSURE RANGE

Natural Gas
Minimum
4.5" W.C. (1.12 kPa)
Maximum
10.5" W.C. (2.61 kPa)
The inlet gas pressure operating range table specifies what the
minimum and maximum gas line pressures must be for the furnace
to operate safely. The gas line pressure MUST BE a minimum of:
• 7" W.C. (1.74 kPA) for Natural Gas
• 11" W.C. (2.74 kPA) for Propane (LP) Gas
in order to obtain the BTU input specified on the rating plate and/or
the nominal manifold pressure specified in these instructions and
on the rating plate.
2.
Once the correct gas inlet pressure has been established, see
Table 15, turn the gas valve to OFF and turn the electrical supply
switch to OFF; then remove the flexible tubing from the gas valve
pressure tap and tighten the pressure tap plug using the 3/32" (2.4
mm) allen wrench.
3.
Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detec-
tion fluid, or other non-flammable leak detection methods.
Read the manifold gas pressure
Connect the positive side of the manometer to the adapter previously
installed in the OUT P Tap on the gas valve. Do not connect any tubing
to the negative side of the manometer, as it will reference atmospheric
pressure. Refer to Figure 34 for connection details.
The cap for the pressure regulator must be removed entirely to gain
access to the adjustment screw. Loosening or tightening the cap
does not adjust the flow of gas.
NOTICE
The regulated outlet pressure has been calibrated at the factory.
Additional pressure adjustment should not be necessary. If adjust-
ment is necessary, set to the following specifications. After adjust-
ment, check for gas leakage.
26
1.
2.
3.
Table 16: Nominal Manifold Pressure
OUTLET
PRESSURE
PORT
WRENCH
BOSS
FIGURE 33: Gas Valve
Propane (LP)
8.0" W.C. (1.99 kPa)
13.0" (3.24 kPa) W.C.
4.
5.
6.
FIGURE 34: Reading Gas Pressure
Refer to Figure 33 for location of pressure regulator adjustment
cap and adjustment screws on main gas valve.
Turn gas and electrical supplies on and follow the operating
instructions to place the unit back in operation.
Adjust manifold pressure by adjusting gas valve regulator screw
for the appropriate gas per the following:

NOMINAL MANIFOLD PRESSURE

Natural Gas
Propane (LP) Gas
INLET
INLET
PRESSURE
ON/OFF SWITCH
PORT
(Shown in ON position)
If gas valve regulator is turned in (clockwise), manifold pressure is
increased. If screw is turned out (counterclockwise), manifold pres-
sure will decrease.
After the manifold pressure has been adjusted, re-calculate the
furnace input to make sure you have not exceeded the specified
input on the rating plate. Refer to "CALCULATING THE FURNACE
INPUT (NATURAL GAS)".
Once the correct BTU (kW) input has been established, turn the
gas valve to OFF and turn the electrical supply switch to OFF; then
remove the flexible tubing from the gas valve pressure tap and
tighten the pressure tap plug using the 3/32" (2.4 mm) Allen
wrench.
Turn the electrical and gas supplies back on, and with the burners
in operation, check for gas leakage around the gas valve pressure
port for leakage using an approved non-corrosive gas leak detec-
tion fluid, or other non-flammable leak detection methods.
MANIFOLD PRESSURE "U" TUBE CONNECTION
MAINIFOLD
PIPE
GAS
BURNERS
OUTLET
PRESSURE TAP
U-TUBE
MANOMETER
Johnson Controls Unitary Products
3.5" w.c. (0.87 kPa)
10.0" w.c. (2.488 kPa)
VENT PORT
OUTLET
MAIN REGULATOR
ADJUSTMENT
FLAME
SENSOR
1/4" TUBING

GAS VALVE

3.5 IN
WATER
COLUMN
GAS
PRESSURE
SHOWN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents