Johnson Controls TM8V MP Series Installation Manual

Residential gas furnace
Table of Contents

Advertisement

Quick Links

INSTALLATION MANUAL
RESIDENTIAL GAS FURNACE MODELS
TM8V*MP, TMLV*MP - 80% AFUE
(Two Stage ECM Multi-position / Low NOx)
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
ELECTRICAL POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Duct Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Vertical Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Coil Flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Horizontal Right Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Horizontal Left Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
PC Series Upflow Coil Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Combustible Floor Base Accessory . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Horizontal Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Typical Attic Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Side Return Cutout Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Coil Projection Dimensions - PC Series Coils . . . . . . . . . . . . . . . . . . 6
Cabinet and Duct Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Nominal Manifold Pressure - High Fire . . . . . . . . . . . . . . . . . . . . . . 11
Nominal Manifold Pressure - Low Fire . . . . . . . . . . . . . . . . . . . . . . . 11
Ratings & Physical / Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . 12
These high efficiency, compact units employ induced combustion, reli-
able hot surface ignition and high heat transfer aluminized tubular heat
exchangers. The units are factory shipped for installation in upflow or
horizontal applications and may be converted for downflow applica-
tions.
These furnaces are designed for residential installation in a basement,
closet, alcove, attic, recreation room or garage and are also ideal for
commercial applications. All units are factory assembled, wired and
tested to assure safe dependable and economical installation and oper-
ation.
These units are Category I listed and may be common vented with
another gas appliance as allowed by the National Fuel Gas Code.
SECTION I: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
LIST OF SECTIONS
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . 20
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . 28
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
LIST OF FIGURES
with Two Stage Variable Speed Furnaces . . . . . . . . . . . . . . . . . . . . 13
Variable Speed Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Combustion Air Inducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Furnace Casing to the Burner Compartment . . . . . . . . . . . . . . . . . . 18
Outside and Ambient Combustion Air . . . . . . . . . . . . . . . . . . . . . . . . 19
Gas Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Reading Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Furnace Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
LIST OF TABLES
Estimated Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unconfined Space Minimum Area . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Free Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Gas Rate (CU FT/HR) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Inlet Gas Pressure Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Nominal Manifold Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Air Flow Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Failure to carefully
read and follow all instructions in this manual can result in fur-
nace malfunction, death, personal injury and/or property dam-
age. Only a qualified contractor, installer or service agency should
install this product.
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
523353-UIM-B-0210

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls TM8V MP Series

  • Page 1: Table Of Contents

    INSTALLATION MANUAL RESIDENTIAL GAS FURNACE MODELS EFFICIENCY TM8V*MP, TMLV*MP – 80% AFUE RATING CERTIFIED ISO 9001 (Two Stage ECM Multi-position / Low NOx) Certified Quality Management System LIST OF SECTIONS SAFETY ..........1 START-UP AND ADJUSTMENTS .
  • Page 2 11. The size of the unit should be based on an acceptable heat loss tions in the manuals and on the labels attached to the unit and calculation for the structure. ACCA, Manual J or other approved other safety precautions that may apply. methods may be used. Johnson Controls Unitary Products...
  • Page 3: Safety

    In some instances these instructions exceed certain local codes and ordinances, especially those who have not kept up with changing residential and non-HUD modular home construction practices. These instructions are required as a minimum for a safe installation. Johnson Controls Unitary Products...
  • Page 4: Unit Clearances To Combustibles

    1. Special floor base or air conditioning coil required for use on combustible floor. 2. Line contact only permitted between lines formed by the intersection of the rear panel and side panel (top in horizontal position) of the furnace jacket and building joists, studs or framing. Johnson Controls Unitary Products...
  • Page 5: Ductwork

    Attach the air conditioning coil cabinet to the duct connector, and then position the furnace on top of the coil cabinet. The connection to the fur- nace, air conditioning coil cabinet, duct connector, and supply air duct must be sealed to prevent air leakage. Johnson Controls Unitary Products...
  • Page 6: Vertical Applications

    PC42, PC43, PC36, PC37 5-1/2 or horizontal PC48 6-1/2 right installations) ALTERNATE PC60 FLANGE LOCATION (Used for downflow or Dimension “C” should be at least 2/3 of dimension “D”. See Figure 6 horizontal left installations) FIGURE 3: Coil Flange Johnson Controls Unitary Products...
  • Page 7: Horizontal Left Or Right Application (Right Shown)

    Refer to the instructions supplied with the duct con- as shown above. It must not be installed on its back. nector for proper installation. Refer to the separate accessory parts list at the end of these instructions for the approved accessory duct con- nectors. Johnson Controls Unitary Products...
  • Page 8: Typical Attic Installation

    Do not use the top return bend of the heat exchangers as lifting points as the tubes may shift out of position or their location brackets/baffles. Johnson Controls Unitary Products...
  • Page 9: Filters

    2. Do not exceed 1800 CFM using a single side return and a 16x25 filter. For CFM greater than 1800, you may use two side returns or one side and the bottom or one return with a transition to allow use of a 20x25 filter. Johnson Controls Unitary Products...
  • Page 10: Gas Piping

    1/2 psig (3.5 kPa). Gas piping may be connected from either side of the furnace using any of the gas pipe entry on both sides of the furnace. Refer to Figure 12. Johnson Controls Unitary Products...
  • Page 11: Electrical Power

    63°F (35°C) rise wire when installed in accordance with instructions. Refer to Table 7 in these instructions for specific furnace electrical data. The residential supply must have a bonded neutral. Johnson Controls Unitary Products...
  • Page 12: Electrical Wiring

    After making the wiring connections replace the wiring box cover and screws. Refer to Figure 16. The furnace's control system requires correct polarity of the power supply and a proper ground connection. Refer to Figure 16. Johnson Controls Unitary Products...
  • Page 13: Thermostat Chart - Single Stage Air Conditioners With Two Stage Variable Speed Furnaces

    Thermostat Installer Setup 15-Compressor Protection -must be set to 5 Part Numbers: Part Number: SAP = Legacy S1-2HU16700124 265904 = 031-09169 449572 FIGURE 17: Thermostat Chart - Single Stage Air Conditioners with Two Stage Variable Speed Furnaces Johnson Controls Unitary Products...
  • Page 14: Thermostat Chart - Single Stage Heat Pump With Two Stage Variable Speed Furnace (Hot Heat Pump Or Conventional)

    Part Number: 18395 = 031-01996 SAP = Legacy S1-2HU16700124 340512 = 031-09178 265904 = 031-09169 449572 FIGURE 18: Thermostat Chart - Single Stage Heat Pump with Two Stage Variable Speed Furnace (Hot Heat Pump or Conventional) Johnson Controls Unitary Products...
  • Page 15: Thermostat Chart - Two Stage Ac With Two Stage Variable Speed Furnace

    E2/P Switch must be in the E2 position Part Numbers: SAP = Legacy 265904 = 031-09169 449572 FIGURE 19: Thermostat Chart - Two Stage AC with Two Stage Variable Speed Furnace Johnson Controls Unitary Products...
  • Page 16: Thermostat Chart - Two Stage Hp With Two Stage Variable Speed Furnace (Hot Heat Pump Or Conventional)

    126768 = 031-09137 Part Numbers: 18395 = 031-01996 SAP = Legacy 340512 = 031-09178 265904 = 031-09169 449572 FIGURE 20: Thermostat Chart - Two Stage HP with Two Stage Variable Speed Furnace (Hot Heat Pump or Conventional) Johnson Controls Unitary Products...
  • Page 17: Vent System

    FIGURE 21: Combustion Air Inducer feet higher than any portion of the building with a horizontal dis- tance of ten feet. The chimney must extend at least 5 ft (1.5 m) above the highest equipment draft hood or flue collar. Johnson Controls Unitary Products...
  • Page 18: Combustion Airflow Path Through The Furnace Casing To The Burner Compartment

    Appliance 1 Appliance 2 Total Input + 30,000 = (130,000  4,000) = 32.5 Sq. In. Vertical 100,000 Appliance 1 Appliance 2 Total Input + 30,000 = (130,000  2,000) = 65 Sq. In. Horizontal 100,000 Johnson Controls Unitary Products...
  • Page 19: Outside And Ambient Combustion Air

    1 square in per 3000 Btu per hour (7.3 cm per kW) of the total input rating of all equipment located in the enclosure. Not less than the sum of all vent connectors in the confined space. Johnson Controls Unitary Products...
  • Page 20: Start-Up And Adjustments

    With the burner assembly out of the way, simply slide the NOx screens out of the heat exchanger tubes and discard the screens. Replace all components in reverse order. Reconnect all wiring. Johnson Controls Unitary Products...
  • Page 21 Burner ignition may not be satisfactory on first startup due to resid- ual air in the gas line or until gas manifold pressure is adjusted. The ignition control will make 3 attempts to light before locking out. Johnson Controls Unitary Products...
  • Page 22: Gas Rate (Cu Ft/Hr)

    Using a 3/32” (2.4 mm) Allen wrench, loosen the set screw by turn- Maximum 10.5” W.C. (2.61 kPa) 13.0” (3.24 kPa) W.C. ing it 1 turn counter clockwise. DO NOT REMOVE THE SET SCREW FROM THE PRESSURE PORT. Johnson Controls Unitary Products...
  • Page 23: Gas Valve

    Table 13: Nominal Manifold Pressure FIGURE 25: Reading Gas Pressure NOMINAL MANIFOLD PRESSURE High Fire Low Fire Natural Gas 3.5" w.c. (0.87 kPa) 1.5" w.c. (0.37 kPa) Propane (LP) Gas 10.0" w.c. (2.488 kPa) 4.2" w.c. (1.04 kPa) Johnson Controls Unitary Products...
  • Page 24: Safety Controls

    Too many supply or return registers closed or blocked off. The control module will lockout if the limit trips 5 consecutive times. If this occurs, control will reset & try ignition again after 1 hour. Johnson Controls Unitary Products...
  • Page 25 R and W terminals. The indoor fan motor runs on the speed selected on the HEAT tap of the control board. Johnson Controls Unitary Products...
  • Page 26 12 RED FLASHES: This code indicates an open igniter circuit, which could be a disconnected or loose wire or a cracked or broken igniter. STEADY ON RED: Control failure. Replace control board. Johnson Controls Unitary Products...
  • Page 27: Air Flow Data

    NOTE: At some settings, LOW COOL and/or LOW HEAT airflow may be lower that what is required to operate an airflow switch on certain models of electronic air clean- ers. Consult the instructions for the electronic air cleaner for further details. * The ADJ “D” tap should not be used. Johnson Controls Unitary Products...
  • Page 28: Replacement Parts List

    3. Customer Service contact information. a. Click on the “Brand Links” button b. Click on the “Customer Service” button • You can contact us by mail. Just send a written request to: Johnson Controls Unitary Products Consumer Relations 5005 York Drive Norman, OK 73069...
  • Page 29: Wiring Diagram

    523353-UIM-B-0210 SECTION X: WIRING DIAGRAM FIGURE 27: Wiring Diagram Johnson Controls Unitary Products...
  • Page 30 NOTES Subject to change without notice. Published in U.S.A. 523353-UIM-B-0210 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: 523353-UIM-A-0809 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...

This manual is also suitable for:

Tmlv mp series

Table of Contents