Gas Pressure Check; Gas Pipe Sizing Chart - Majestic fireplaces UV36RN Homeowner's Installation And Operating Instructions Manual

Vent-free gas fireplaces
Table of Contents

Advertisement

When installing this fireplace at an elevation above
2,000 feet, it may be necessary to decrease the input
rating by changing the existing burner orifice to a small-
er size. Input should be reduced four percent (4%) for
each 1,000 feet above sea level, unless the heating
value of the gas has been reduced, in which case this
general rule will not apply. To identify the proper orifice
size, check with the local gas utility.
Consult your local gas utility for assistance in determin-
ing the proper orifice for your location.

Gas Pressure Check

The gas inlet pressure specified in Table 1 is the pres-
sure where the field-installed gas line connects to the
gas control. This is measured at the inlet test port on
the gas valve in the appliance. Ensure that pressure is
as shown in Table 1.
The manifold pressure is controlled by a regulator built
into the gas control and should be checked at the pres-
sure test points located between the flame adjustment
knob and the control knob at the front of the valve. The
NOTE: To determine the size of the branch gas line from the main gas line to the fireplace, enter the tables below (for
iron pipe or copper tubing) using the distance from the gas meter or second stage regulator to the furthest appliance on
the gas system. Select a pipe or tube diameter which has enough capacity to meet the maximum input requirement of
the fireplace. Regardless, do not use less than 1/2" diameter for the branch line. For any distances required longer than
shown in these tables, refer to the National Fuel Gas Code.
NOTE: There may be a local gas utility requirement specifying a minimum diameter for gas piping. All units require a 1/2 inch pipe con-
nection at the gas valve.
Length
of
1/2" D
Pipe
Natural
20'
92
30'
73
40'
63
50'
56
60'
50
70'
46
90'
40
100'
38
Tubing Length
Feet
10
20
30
40
50
60
80
100
WARNING: Use only internally tinned copper tubing. If correct copper tubing is not used, tubing can deteriorate and de-
velop gas leaks.
20007436
Gas Line Pipe Sizing
CAPACITY OF PIPING
Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Natural Gas - 0.6 (1000 BTU/Cubic Foot)
Specific Gravity for Propane Gas - 1.6 (2550 BTU/Cubic Foot)
Nominal Inches for Iron Pipe Sizes (1,000s BTU/hr)
3/4" D
Propane
Natural
Propane
143
190
296
115
152
237
97
130
202
87
115
179
79
105
163
71
96
151
61
84
130
59
79
122
Outside Diameter Copper Tubing, Type L (1,000s BTU/hr)
1/2"
0.43
110
76
61
52
46
42
36
32
UV36RN/RP Vent-Free Gas Fireplaces
pressure connections accept 1/4" I.D. hose or tubing.
The pressure should be checked with the appliance
burning on high (highest setting) and all other gas ap-
pliances turned on. One must then read the manometer
and if pressures are not as specified in Table 1, then
the inlet pressure must be adjusted.
After measuring the pressure, tighten the screw in the
pressure test port and check for leaks. Replace the
control box cover and the two screws.
Table 1
Gas Inlet Pressure
Max.
Normal
Min.*
Regulator Pressure
*Minimum inlet supply pressure for the purpose of input adjustment.
CAUTION: If the appliance's operating pressures
are not checked and adjusted, improper combus-
tion may result in soot being produced.
1" D
Natural
Propane
Natural
350
546
730
285
444
590
245
380
500
215
334
440
196
304
400
180
280
370
160
250
320
150
235
305
5/8"
3/4"
0.545
0.666
206
348
141
239
114
192
97
164
86
146
78
132
67
113
59
100
Natural
14.0" w.c.
7.0" w.c.
4.5" w.c.
3.5" w.c.
1¹⁄₄" D
1¹⁄₂" D
Propane Natural
1135
1100
918
890
778
760
683
670
622
610
576
560
497
490
474
460
7/8"
0.785
536
368
296
256
224
203
174
154
Propane
14.0" w.c.
11.0" w.c.
11.0" w.c.
10.0" w.c.
Propane
1711
1385
1183
1043
949
872
763
717
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uv36rp

Table of Contents