Rheem R-410A Installation Instructions Manual page 35

Prl-jec series two-stage heat pump outdoor units
Hide thumbs Also See for R-410A:
Table of Contents

Advertisement

• Each fault is displayed one time with the top right hand segment of the dual 7-
segment display activated between faults.
• Each fault is displayed with the most recent fault displayed first.
• A maximum of six individual faults can be stored
• A maximum of three consecutive identical faults are stored.
• A "0" will be displayed with no faults are stored
• The ICC will automatically exit the F F A A U U L L T T R R E E C C A A L L L L mode after displaying stored
faults
I I M M P P O O R R T T A A N N T T : : The ICC stores the previous six history faults. The complete stored
fault history cannot be displayed using a conventional thermostat.
Fault Recall Mode (TEST and SW2 Buttons)
C C l l e e a a r r F F a a u u l l t t H H i i s s t t o o r r y y ( ( T T E E S S T T a a n n d d S S W W 2 2 B B u u t t t t o o n n s s ) )
Enter FAULT RECALL mode by pressing the TEST and SW2 buttons at the same time
• Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) sec-
with insulated probes for one (1) second and release.
onds with insulated probes and release.
When entering and exiting FAULT RECALL mode the top and bottom segments of the 7-
• The top and bottom segments of the dual 7-segment LEDs flash to indicate the
segment LEDs will illuminate.
history has been cleared.
Fault history is cleared with the top and bottom LED
segments flash
Fault Recall Mode – the top and bottom segments illuminated
When entering FAULT RECALL mode, the ICC will automatically scroll through stored
faults on the 7-segment LEDs.
Each fault is displayed one time with the top segment of the 7-segment display activated
between faults.
Each fault is displayed with the most recent fault displayed first.
A maximum of six individual faults can be stored
A maximum of three consecutive identical faults are stored.
A "0" will be displayed with no faults are stored
The ICC will automatically exit the FAULT RECALL mode after displaying stored faults
IMPORTANT: The ICC stores the previous two weeks of history faults. The complete stored
fault history cannot be displayed using a conventional thermostat.
Clear Fault History (TEST and SW2 Buttons)
Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) seconds with
insulated probes and release.
The top and bottom segments of the 7-segment LEDs flash to indicate the history has been
cleared.
Fault history is cleared with the top and bottom LED segments flash
8
35