• Each fault is displayed one time with the top right hand segment of the dual 7-
segment display activated between faults.
• Each fault is displayed with the most recent fault displayed first.
• A maximum of six individual faults can be stored
• A maximum of three consecutive identical faults are stored.
• A "0" will be displayed with no faults are stored
• The ICC will automatically exit the F F A A U U L L T T R R E E C C A A L L L L mode after displaying stored
faults
I I M M P P O O R R T T A A N N T T : : The ICC stores the previous six history faults. The complete stored
fault history cannot be displayed using a conventional thermostat.
Fault Recall Mode (TEST and SW2 Buttons)
C C l l e e a a r r F F a a u u l l t t H H i i s s t t o o r r y y ( ( T T E E S S T T a a n n d d S S W W 2 2 B B u u t t t t o o n n s s ) )
Enter FAULT RECALL mode by pressing the TEST and SW2 buttons at the same time
•
• Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) sec-
with insulated probes for one (1) second and release.
onds with insulated probes and release.
When entering and exiting FAULT RECALL mode the top and bottom segments of the 7-
•
• The top and bottom segments of the dual 7-segment LEDs flash to indicate the
segment LEDs will illuminate.
history has been cleared.
Fault history is cleared with the top and bottom LED
segments flash
Fault Recall Mode – the top and bottom segments illuminated
When entering FAULT RECALL mode, the ICC will automatically scroll through stored
•
faults on the 7-segment LEDs.
Each fault is displayed one time with the top segment of the 7-segment display activated
•
between faults.
Each fault is displayed with the most recent fault displayed first.
•
A maximum of six individual faults can be stored
•
A maximum of three consecutive identical faults are stored.
•
A "0" will be displayed with no faults are stored
•
The ICC will automatically exit the FAULT RECALL mode after displaying stored faults
•
IMPORTANT: The ICC stores the previous two weeks of history faults. The complete stored
fault history cannot be displayed using a conventional thermostat.
Clear Fault History (TEST and SW2 Buttons)
Clear FAULT HISTORY by pressing both TEST and SW2 button for five (5) seconds with
•
insulated probes and release.
The top and bottom segments of the 7-segment LEDs flash to indicate the history has been
•
cleared.
Fault history is cleared with the top and bottom LED segments flash