Set Thermostat Heat Anticipator
When using a non- -electronic thermostat, the thermostat heat
anticipator must be set to match the amp draw of components in
the R- -W/W1 circuit. Accurate amp draw measurements can be
obtained only at the thermostat subbase terminals R and W.
The thermostat and anticipator should NOT be in the circuit while
measuring current. If thermostat has no subbase, the thermostat
must be disconnected from R and W/W1 wires during current
measurement.
Fig. 63 illustrates an easy method of obtaining thermostat amp
draw measurements. The amp reading should be taken after blower
motor has started and furnace is operating in low- -heat.
1. To operate furnace in low- -heat, turn setup switch SW1- -2 to
ON position (See Fig. 33) and connect ammeter leads across
thermostat subbase R- -W.
2. See thermostat manufacturer's instructions for adjusting the
heat anticipator and for varying heating cycle length.
NOTE: When using an electronic thermostat, set cycle rate for 3
cycles per hr.
3. Return setup switch SW1- -2 to OFF position and replace
thermostat on subbase.
Check Safety Controls
This section covers the safety controls that must be checked before
the installation is complete. The flame sensor, gas valve, and
pressure switches were all checked in the Start- -up procedure
section as part of normal operation.
Check Primary Limit Control
This control shuts off the gas control system and energizes the
air- -circulating blower motor if furnace overheats.
1. The recommended method of checking this limit control is
to gradually block off return air after furnace has been
operating for a period of at least 5 minutes.
2. As soon as limit control has shut off burners, a status code
33 will appear on furnace control.
3. The return- -air opening should be unblocked to permit
normal air circulation.
THERMOSTAT SUBBASE
TERMINALS WITH
THERMOSTAT REMOVED
(ANITICIPATOR, CLOCK, ETC.,
MUST BE OUT OF CIRCUIT.)
R Y W G
10 TURNS
FROM UNIT 24-V
CONTROL TERMINALS
5.0 AMPS ON AMMETER
EXAMPLE:
10 TURNS AROUND JAWS
Fig. 63 - - Amp Draw with Ammeter
By using this method to check the limit control, it can be
established that the limit is functioning properly and the furnace
will operate safely if there is a restricted return- -air duct or motor
failure. If the limit control does not function during this test, the
cause must be determined and corrected.
Check Pressure Switches
This control proves operation of the draft inducer. Check switch
operation as follows:
1. Turn off 115- -v power to furnace.
2. Remove control access door and disconnect inducer motor
12- -pin wire harness at inducer motor.
3. Turn on 115- -v power to furnace.
4. Set thermostat to "call for heat." When pressure switches are
functioning properly, status code 42 will flash on furnace
control approximately 20 sec after thermostat switch is
closed. If either a status code 31 or 32 is flashed when
inducer motor is disconnected, the furnace will shut itself
down immediately. Determine the reason pressure switches
did not function properly and correct the condition.
5. Turn off 115- -v power to furnace.
6. Reconnect inducer motor wire harness. Reinstall furnace
access door.
7. Turn on 115- -v power to furnace.
8. Reset thermostat to desired temperature.

CHECKLIST

1. Put away tools and instruments. Clean up debris.
2. Verify flame rollout manual reset switch has continuity.
3. Verify that blower and main access doors are properly
installed.
4. Cycle test furnace with room thermostat.
5. Check
operation
of accessories
instructions.
6. Review User's Manual with owner.
7. Leave literature packet near furnace.
HOOK-AROUND
AMMETER
= 0.5 AMPS FOR THERMOSTAT
ANTICIPATOR SETTING
60
per manufacturer's
A96316