CONDENSATE DRAIN

General
Condensate trap is shipped installed in the blower shelf and factory
connected for UPFLOW applications. Condensate trap must be
RELOCATED for use in DOWNFLOW and HORIZONTAL
applications.
Condensate trap MUST be used for all applications.
An external trap is not required when connecting the field drain to
this condensate trap.
The field drain connection (condensate trap or drain tube coupling)
is sized for 1/2- -in. CPVC, 1/2- -in. PVC, or 5/8- -in. ID tube
connection.
Drain pipe and fittings must conform to ANSI standards and
ASTM D1785, D2466, or D2846. CPVC or PVC cement must
conform to ASTM D2564 or F493. Primer must conform to
ASTM F656. In Canada, use CSA or ULC certified schedule 40
CPVC or PVC drain pipe, fittings, and cement.
When a condensate pump is required, select a pump which is
approved for condensing furnace applications. To avoid
condensate spillage, select a pump with an overflow switch.
Furnace condensate is mildly acidic, typically in the pH range of
3.2 to 4.5. Due to corrosive nature of this condensate, a condensate
pH neutralizing filter may be desired. Check with local authorities
to determine if a pH neutralizer is required.
Table 8 – Vent Termination Kit for Direct Vent/2-Pipe System
TERMINATION SYSTEM
Single Penetration of Wall or Roof
Single Penetration of Wall or Roof
2--- Pipe Termination System
2--- Pipe Termination System
A94054
DIAM. OF COMBUSTION AIR AND VENT
1, 1--- 1/2, 2, or 2--- 1/2 (25, 38, 51, 64 mm)
2--- 1/2, 3 or 4 (64, 76, 102 mm)
1, 1--- 1/2 or 2 (25, 38, 51mm)
2--- 1/2, 3 or 4 (64, 76, 102 mm)
Application
The furnace, A/C, and humidifier drains may be combined and
drained together. The A/C drain must have an external,
field- -supplied trap prior to the furnace drain connection. All drain
connections (furnace, A/C, or humidifier) must be terminated into
an open or vented drain as close to the respective equipment as
possible to to prevent siphoning of the equipment's drain.
CONDENSATE TRAP
WIRE TIE(S)
HEAT TAPE
(3 WRAPS MINIMUM)
Fig. 46 - - Condensate Trap Heat Tape
See Fig. 45 for example of possible field drain attachment using
1/2- -in. CPVC or PVC tee for vent and A/C or humidifier drain
connection.
Outdoor draining of the furnace is permissible if allowed by local
codes. Caution should be taken when freezing ambient may freeze
drain pipe and prohibit draining.
WARNING
!
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal
injury or death.
Caution should be taken to prevent draining where slippery
conditions
may
cause
condensate draining may cause saturated soil conditions
which may result in damage to plants.
Condensate Drain Protection
Freezing condensate left in condensate trap and drain line may
cause cracks, and possible water damage may occur. If freeze
protection is required, use condensate freeze protection accessory
or equivalent 3 to 6 watt per ft. (.3M) at 120v and 40_F (4.4_ C)
self- -regulating, shielded, and waterproof heat tape. See Installation
Instructions supplied with accessory or heat tape manufacturer's
recommendations.
1. Fold heat tape in half and wrap on itself 3 times.
43