Checking Correct Grounding - Samsung UH140GAMC Installation Manual

System air conditioner (cooling and heating)
Hide thumbs Also See for UH140GAMC:
Table of Contents

Advertisement

Checking correct grounding

Carbon
Steel
plastic
core
Terminal M4
PVC-insulated green/
yellow wire
50cm
30cm
22
22
E-
E-
If the power distribution circuit does not have an earth or the ground does
not comply with specifications, an grounding electrode must be installed.
The corresponding accessories are not supplied with the air conditioner.
Select an grounding electrode that complies with the specifications given in
1
the illustration.
To
Determine a suitable location for the grounding electrode:
2
grounding
 In damp hard soil rather than loose sandy or gravel soil that has a
screw
higher grounding resistance
Away from underground structures or facilities, such as gas pipes,

water pipes, telephone lines and underground cables
 At least two metres away from a lightening conductor grounding
electrode and its cable
Note
Finish wrapping insulating tape around the rest of the pipes leading to the
3
outdoor unit.
Install a green/yellow coloured grounding wire:
4
If the grounding wire is too short, connect an extension lead, in a

mechanical way and wrapping it with insulating tape (do not bury the
connection)
Secure the grounding wire in position with staples

Note
Carefully check the installation, by measuring the grounding resistance with
5
a ground resistance tester. If the resistance is above required level, drive the
electrode deeper into the ground or increase the number of grounding
electrodes.
Connect the grounding wire to the electrical component box inside of the
6
outdoor unit.
The grounding wire for the telephone line cannot be used to

ground the air conditioner.
If the grounding electrode is installed in an area of heavy traf-

fic, its wire must be connected securely.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uh105gamc

Table of Contents