Samsung UH140GAMC Installation Manual page 11

System air conditioner (cooling and heating)
Hide thumbs Also See for UH140GAMC:
Table of Contents

Advertisement

Power Cable Specifications
Type of
outdoor
unit
Power
Max/Min
Supply
(V)
380-415V~
A
/50HZ
±10%
380-415V~
±10%
B
/50HZ
 T he power cable is not supplied with air conditioner.
For power cable, use the grade H07RN-F or H05RN-F materials.
Between Indoor and Outdoor Connection Cord Specifications
Power Supply (Single Phase)
Max/Min(V)
Power Supply
220-240V~/50Hz
10%
±
For connection cord, use the grade H07RN-F or H05RN-F materials.
Power Supply
3 Phase
Power
MCCB
ELB
Length
Cable
2.5mm 2 ,
10m
4 Wires
Frame:
or less
30A
20A
3.0mm 2 ,
Trip:
20m
4 Wires
20A
or less
2.0mm 2 ,
10m
Frame:
4 Wires
or less
30A
20A
Trip:
2.5mm 2 ,
20m
20A
4 Wires
or less
Earth Cable
Connection
Wire
2.5mm 2
Ø 1.6mm
2 wires
1 wire
Single Phase
Power
Max/Min
MCCB
ELB
Supply
(V)
-
-
-
-
-
-
-
-
Communication
Home server
Cable
0.75~
1.25mm 2
1.25mm 2
2 wires
2 wires
Earth
Cable
Power
Length
Cable
-
-
Ø1.6mm,
1 Wire
-
-
0.75~
11