8) Corner panel installation

Hook the corner panel strap to the pin on the decorator panel as shown in the figure.
Insert part
screw.
9) Installing the air inlet grille
• Install the air return grille by following the removal procedure (item 4) in reverse order.
Note (1) : Match up the installation position of the panel's striker and the "Pull" character position direction on the surface of the grille. If these do not
match, the striker could be damaged.

(3) Ceiling suspended type (FDEN)

(a) Selection of installation location
1) A place where good air circulation and delivery can be obtained.
Cold air throw
odel
Air throw
Conditions
(1)
Installation height: 2.4 ~ 3.0 m above the floor
(2)
Fan speed: Hi
(3)
Location: Free space without obstacles
(4)
Distance of reach indicates the horizontal distance after the wind touched down the floor.
(5)
Air velocity at the throw: 0.5 ( m/sec.)
2) A place where ceiling has enough strength to support the unit.
3) A place where there is no obstruction to the return air return and supply air supply ports.
4) Places exposed to oil splashes or steam (e.g. kitchens and machine plants).
Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or damage
in molded synthetic resin parts.
5) A place where the space shown below may be secured.
on the corner panel in part
Pin
FDENA151R, 201R
FDENA251R, 301R
7.5
Ceiling mouting installation
100 or more
150 or more
Obstacle
on the decorator panel, then fit the 2 claws and fasten the corner panel
Screw
FDENA401R, 501R, 601R
8
9
Unit : mm
5 or more
196
-
-
Pin
A
Claws
Unit : m
Note (1) In the case of neighboring installations,
separate the units by the following
dimensions or greater.
Item
Dimensions
Model
FDENA151R, 201R
4000
FDENA251R, 301R
4500
FDENA401R, 501R, 601R
5000
a