Trane TAYSTAT 575 Installation Instructions Manual page 6

Electronic heat pump thermostat
Table of Contents

Advertisement

ELECTRONIC HEAT PUMP THERMOSTAT
Select
Degree temperature
display
Extended fan operation in
heating
Extended fan operation in
cooling
Outdoor temperature
display (select models)
Comfort-R Enable
Minimum deadband
between heating and
cooling in auto
changeover mode
Minimum on time (heat)
Minimum on time
(cooling)
Temperature range stops
in heating
Temperature range stops
in cooling
Pub. No. 11-HD28D2-1
69-1591–1
Table 2. Thermostat Installer Setup Options (Continued).
Installer
Setup Number
Display
14
00
19
00
20
00
24
00
28
00
30
04
32
10
33
10
34
85
35
65
Factory-Setting
Description
Temperature displays in
°F
No extended fan
operation after the call
for heat ends
No extended fan
operation after the call
for cool ends
No outdoor temperature
displays.
No fan delay
Heating and cooling
setpoints can be set no
closer than 4°F (2°C)
Ten-minute minimum on
time for compressor
(heating)
Ten-minute minimum on
time for compressor
(cooling)
Highest heating
sepoint setting
Lowest cooling
sepoint setting
6
Other Choices
(Press
or
key to change)
Display
Description
01
Temperature displays in °C
01—Fan operation exends
01, 02
30 seconds after the call
or 03
ends
02—Fan operation exends
60 seconds after the call
ends
03—Fan operation exends
90 seconds after the call
ends
01—Fan operation exends
01, 02
30 seconds after the call
or 03
ends
02—Fan operation exends
60 seconds after the call
ends
03—Fan operation exends
90 seconds after the call
ends
01
Outdoor temperature is
displayed. Needs a
TAYSENS100A Outdoor
Sensor
01—30 seconds (maximum
01 or
delay)
02
02—15 seconds (maximum
delay)
03 thru
Heating and cooling
10
setpoints can be set no
closer than the chosen
value:
3—3°F (1.5°C)
4—4°F (2°C)
5—5°F (2.5°C)
6—6°F (3°C)
7—7°F (3.5°C)
8—8°F (4°C)
9—9°F (4.5°C)
10—10°F (5°C)
00 thru
Minimum number of minutes
15
(0 thru 15) the compressor is
on during call for heat
00 thru
Minimum number of minutes
15
(0 thru 15) the compressor is
on during call for cool
01
Temperature range (1°F
increments) of heating
setpoint setting
Temperature range (1°F
increments) of cooling
setpoint setting