Code 2
DHW
(continued)
Coding in the factory setting
63:0 (NOT USED)
65:0
DO NOT ADJUST
6C:100
NOT USED
6F:...
71:0
72:0
73:0
58
Without auxiliary function for
DHW heating
Information regarding the
type of diverter valve (not
adjustable):
0: No diverter valve
1: Viessmann diverter valve
2: Wilo diverter valve
3: Grundfos diverter valve
Set speed, internal circulation
pump with DHW heating 100%
Maximum output for DHW
heating in %, specified by
the boiler coding card
DHW circulation pump: "ON"
in accordance with the time
program
DHW circulation pump: "ON"
in accordance with the time
program
DHW circulation pump: "ON"
in accordance with the time
program
Vitodens 222-F B2TA 19 and 35 Service
Possible change
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14 days.
to
63:14
63:15
2 x daily
--
6C:0
Set speed adjustable from
to
0 to 100%.
6C:100
6F:0
Maximum output for DHW heating
to
adjustable from minimum output
6F:100
to 100%.
71:1
"OFF" during DHW heating
to first set value.
71:2
"ON" during DHW heating
to first set value.
72:1
"OFF" during DHW heating
to second set value.
72:2
"ON" during DHW heating
to second set value.
73:1
"ON" from once per hour for 5
to
minutes up to 6 times per hour
73:6
for 5 minutes during the time
program.
73:7
Constantly "ON".
--