11.2
E18JKK-1
11.2.1
Select the Best Location
11.2.1.1
Indoor Unit
•
Do not install the unit in excessive oil fume areas
such as kitchens, workshops and etc.
•
There should not be any heat source or steam
near the unit.
•
There should not be any obstacles blocking the air
circulation.
•
A place where air circulation in the room is good.
•
A place where drainage can be easily done.
•
A place where noise prevention is taken into
consideration.
•
Do not install the unit near a door.
•
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
•
Recommended installation height for indoor unit
shall be at least 8.2 ft.
11.2.1.2
Outdoor Unit
•
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
•
There should not be any animal or plant which
could be affected by hot air discharged.
•
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
•
Do not place any obstacles near the unit which
may cause a short circuit of the discharged air.
•
If piping length is over the [piping length for
additional gas], additional refrigerant should be
added as shown in the table.
•
Recommended installation height for outdoor unit
should be above the seasonal snow level.
Example: For E18JKK-1
If the unit is installed at 41.0 ft distance, the quantity of
additional refrigerant should be 1.64 oz .... (41 - 32.8)
ft x 0.2 oz/ft = 1.64 oz.
11.2.2
Indoor/Outdoor Unit Installation
Diagram