Appliance Operation - Potterton Performa System 12 HE Installation & Service Instructions Manual

Wall mounted powered flue condensing boiler gas fired central heating unit
Hide thumbs Also See for Performa System 12 HE:
Table of Contents

Advertisement

Boiler Primary Circuit
16
17
13
15
14
11
Key
1
Heat Exchanger
2
Burner
3
Ignition Electrode
4
Flame Sensing Electrode
5
Gas Valve
6
Pump
7
Automatic Air Vent
8
Pressure Relief Valve
9
Boiler Drain Point
10
Gas Inlet
11
Boiler Flow
12
Boiler Return
13
Pressure Gauge
14
Automatic By-Pass
15
Hydraulic Differential Pressure Sensor
16
Safety Thermostat
17
Temperature Sensor
18
Expansion Vessel
19
Temperature Sensor
20
Secondary Heat Exchanger
8
1
2
3
4
6
5
18
10
3.0

APPLIANCE OPERATION

3.1
Operating Mode (Fig. 2)
1. With a demand for heating, the pump circulates
water through the primary circuit. At a pre-determined
flow rate the hydraulic differential pressure switch
operates, initiating the ignition sequence.
20
2. The main burner ignites at low rate, then the gas
valve controls the gas rate to maintain the heating
19
temperature measured by the temperature sensor.
3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the
7
burner relights automatically (anti-cycling). The pump
continues to run during this period.
4. When the demand is satisfied the burner is
extinguished and the pump continues to run for a
period of 3 minutes (Pump Overrun).
IMPORTANT: When the selector switch is in the
'0' (Off) position the electrical supply to the boiler is
8
isolated. The boiler will not operate.
9
3.2
Frost Protection Mode
1. The frost protection mode is integral to the
appliance and functions when the selector switch (see
Section 2.1) is in the ON position (
system temperature falls below 5° C then the boiler
will fire on its minimum setting until a flow
temperature of 30° C is reached. Further protection
can be incorporated by using a system frost
12
thermostat.
Fig. 2
3.3
Pump Protection
1. With the selector switch (see Section 2.1) in the
ON position (
operate for 1 minute in every 24 hours to prevent
sticking.
). If the
) the pump will automatically
Publication No. 5111817