Venting Installation; Installation Precautions; Venting Requirements - Vermont Castings VCFDVI31 Installation And Operating Instructions Manual

Clean face direct vent fireplace insert firebox
Table of Contents

Advertisement

VeNtING INstAllAtION

Read all instructions completely and
thoroughly before attempting installation.
Failure to do so could result in serious injury,
property damage or loss of life. Operation of
improperly installed and maintained venting
system could result in serious injury,
property damage or loss of life.
Failure to follow these instructions will void
the warranty.

INstAllAtION pReCAutIONs

Consult local building codes before beginning the installa-
tion. The installer must make sure to select the proper vent
system for installation. Before installing vent kit, the installer
must read this insert manual and vent kit instructions.
Only a qualified installer/service person should install vent-
ing system. The installer must follow these safety rules:
Wear gloves and safety glasses for protection.
Use extreme caution when using ladders or when
on rooftops.
Be aware of electrical wiring locations in walls and
ceiling.
The following actions will void the warranty on your vent-
ing system:
Installation of any damaged venting component.
Unauthorized modification of the venting system.
Installation of any component part not manufactured
or approved by MHSC.
Installation other than permitted by these instruc-
tions.
this insert must be vented to the outside.
the venting system must NeVeR be
attached to a chimney serving a separate
solid fuel burning appliance. each gas
appliance must use a separate vent system.
Do not use common vent systems.
20304166

VeNtING RequIReMeNts

Make sure the exhaust pipe on heater
connects to exhaust portion of cap. At-
tach flex liners. Figure 9
Do not crimp or rupture liner when bend-
ing it into chimney offsets.
The exhaust vent must reline the entire length of chim-
ney and terminate above chimney top.
Vent must meet all vent manufacturer's requirements
when installed.
Make sure you have the following before installing
unit:
3" and 3" UL 1777 Listed gas liner for air inlet and
exhaust.
Vertical Terminations kits: HEDV32T812,
HEDV32T1212
Inlet
Figure 9 -
Venting Unit
FP2947
vent requirements
VCFDVI31 Gas Fireplace Insert
Exhaust
Maximum Height 40'
(12.9 m)
Minimum Height 10'
(3 m)
FP2947
11