Bryant 340AAV Installation, Start-Up, And Operating Instructions Manual page 10

4-way multipoise fixed-capacity condensing gas furnace
Table of Contents

Advertisement

DRAIN TUBE
COUPLING
Fig. 8 - - Downflow Tube Configuration
(Right-Hand Trap Installation)
h. Install drain tube coupling grommet (factory-supplied
in loose parts bag) in selected casing hole.
i. Slide drain tube coupling (factory-supplied in loose
parts bag) through grommet ensuring long end of
coupling faces blower.
j. Cement 2 factory-supplied 1/2-in. (13 mm) street
CPVC elbows to the rigid drain tube connection on the
condensate trap. (See Fig. 6.) These elbows must be
cemented together and cemented to condensate trap
drain connection.
NOTE: Failure to use CPVC elbows may allow drain to kink
and prevent draining.
k. Connect larger diameter drain tube and clamp
(factory-supplied in loose parts bag) to condensate trap
and clamp securely.
l. Route tube to coupling and cut to appropriate length.
m. Attach tube to coupling and clamp securely.
CONDENSATE TRAP LOCATION (ALTERNATE
UPFLOW ORIENTATION)
An alternate location for the condensate trap is the left-hand side
of casing. (See Fig. 2 and 7.)
NOTE: If the alternate left-hand side of casing location is used,
the factory-connected drain and relief port tubes must be
disconnected and modified for attachment. See Condensate
Trap Tubing
(Alternate
Upflow
tubing attachment.
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
CONDENSATE
TRAP
COLLECTOR BOX
EXTENSION
DRAIN TUBE
A00296
Orientation)
section
for
- - 10 - -
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
Fig. 9 - - Downflow Tube Configuration
(Left-Hand Trap Installation)
To relocate condensate trap to the left-hand side, perform
the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose
parts bag) into blower shelf hole where trap was removed.
WARNING
!
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
products
being
drawn
equipment room.
4. Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING (ALTERNATE
UPFLOW ORIENTATION)
NOTE: See Fig. 7 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain Tube
Connect collector box drain tube (blue label) to
condensate trap.
A00262
in
from
appliances
in
the

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents