Function Details
3.2.6 Room Thermostat Control
Based on the difference between the set temperature by remote controller and indoor unit
suction air temperature, the thermo. is turned on and off.
T = Indoor suction air temperature – temperature set by remote controller (Cooling)
T = Temperature set by remote controller – indoor suction air temperature (Heating)
Thermostat ON Condition
T > +0.5°C
Thermostat OFF Condition
104
• ∆T ≤ – 0.5°C continues for 1 minute (for RZQG71L)
• ∆T ≤ – 0.5°C continues for 1 minute
or
• 5 minutes or more after start up
•&
(for RZQG100 - 140L)
• ∆T ≤ – 2°C (Cooling)
• ∆T ≤ – 2.5°C (Heating)
When changed suddenly from ∆T ≥ +1.5°C to ∆T ≥ -0.5°C
ESIE12-06
Function and Control