Clearance To Combustibles; Mantels; Hearth - Majestic fireplaces NVC36 Operating Instructions Manual

Decorative gas fireplace
Table of Contents

Advertisement

NVC Series B-Vent

Clearance to Combustibles

Appliances
Top .......................................................... 0" (0 mm)
Bottom ..................................................... 0" (0 mm)
Side ......................................................... 0" (0 mm)
Back ........................................................ 0" (0 mm)
Perpendicular Sidewall ........................... 0" (0 mm)
Top of unit to ceiling .......................... 36" (914 mm)
Front of unit to combustibles ............. 36" (914 mm)
Venting
B-Vent ................................................... 1" (25 mm)

Mantels

The height that a combustible mantel is fitted above the
fireplace is dependent on the depth of the mantel. This
also applies to the distance between the mantel leg (if
fitted) and the fireplace.
For the correct mounting height and widths refer to
Figures 2a and 2b and the Mantel Chart below.
The distances and reference points are not affected by
the fitting of a bay window front trim kit.
Noncombustible mantels and legs may be installed at
any height and width around the appliance.
When using a paint or lacquer to finish the mantel,
such paint or lacquer must be heat resistant to prevent
discoloration.
Side View
A
B
C
D
Bottom of Door Trim
Ref.
Mantel
CFM146
Shelf Depth
DV Mantel Chart
7/5/01 sta
V
10" (254 mm)
W
8" (203 mm)
X
6" (152 mm)
Y
4" (101 mm)
Z
2" ( 51 mm)
Fig. 2a Mantel clearances.
6
V
W
X
Y
Z
E
Fireplace
Top Louvre Assembly
Top of
Combustion Chamber
Ref.
Mantel From Top
of Comb. Chamber
A
19¹⁄₂" (495 mm)
B
17¹⁄₂" (444 mm)
C
15¹⁄₂" (394 mm)
D
13¹⁄₂" (343 mm)
E
11¹⁄₂" (292 mm)
Black
Surround
Face
CFM164
CFM164a
Side of
Combustion Chamber
Mantel Leg Chart
06/22/01 sta
Ref.
F
G
H
I
J
Fig. 2b Combustible mantel leg minimum installation.
A hearth is not mandatory but is recommended for
aesthetic purposes. We recommend a noncombustible

hearth.

CFM146
Cold climate installation recommendation: When
installing this unit against a noninsulated
exterior wall or chase, it is mandatory that
the outer walls be insulated to conform to
applicable insulation codes.
Mantel
Leg
Mantel
Ref.
Mantel Leg From Side
Leg Depth
CFM170
10" (254 mm)
K
DV Builder Front
8" (203 mm)
L
View
6" (152 mm)
M
4" (101 mm)
N
2" ( 51 mm)
O
Hearth
J
I
H
G
F
K
L
M
N
O
CFM170
of Comb. Opening
12" (305 mm)
10" (254 mm)
8" (203 mm)
6" (152 mm)
4" (101 mm)
20000194