Central Control Address Number Setting; Setting By Remote Controller On Indoor Unit Side - Toshiba RAV-SM562KRT-E Service Manual

Hi wall type (indoor unit)
Hide thumbs Also See for RAV-SM562KRT-E:
Table of Contents

Advertisement

3.1.8 Central Control Address Number Setting

To connect an indoor unit to the central control remote controller, an address number for central control
must be set.
An address number for central control is indicated as the refrigerant line number of the remote
controller.

1. Setting by Remote Controller on Indoor Unit Side

<Procedure> Perform the following steps in the operation OFF
mode.
Press
and
1
or more.
When group control is going, UNIT No.
and all indoor units in the group are selected. At this time, the
fans of all the selected indoor units start running. (Fig. 1)
Maintain this state without pressing
For individual remote controllers without group control, a
refrigerant line address and an indoor unit address are
indicated.
Specify code
2
Choose setting data with
3
Table 1 shows setting data.
Press
Indication on the LCD shows normal operation.
4
• To change an item for setting, return to
Press
to return to the normal indication.
5
on the R/C simultaneously for 4 seconds
with
buttons.
buttons.
is displayed first,
.
.
2
70
(Fig. 1)
4
3
2
5
Table 1
Setting data
Address No. for central control
0001
1
0002
2
0003
3
0064
64
0099
Not set (factory setting)
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sm802krt-eRav-sm5661krt-eRav-sm801krt-e

Table of Contents