Jra Capacity Measurement Mode (Wired R/C Only); Function Select Setting - Toshiba RAV-SM562KRT-E Service Manual

Hi wall type (indoor unit)
Hide thumbs Also See for RAV-SM562KRT-E:
Table of Contents

Advertisement

1.4 JRA Capacity Measurement Mode (wired R/C only)

Preliminary operation
Press
,
, and
1
In the group control mode, the header unit number is displayed first.
Each pressing of
2
Choose the main indoor unit (connected to the outdoor unit) for which this control is to be performed.
The fan and flap of the selected indoor unit start working.
Specify DN "91" with
3
Set the following data with
4
Data
Rating
0001
Middle
0002
Press
Indication on the LCD shows normal operation.
5
Press
to return the operation mode to normal OFF.
6
Use this mode to measure JRA capacity.
Use this mode under the conditions of JIS B8615-1.
Perform the settings in the table by remote
controller.
Execution procedure
• Press
on the R/C.
To reexecute JRA capacity measurement, repeat steps from step
Once this measurement is completed, the above setting is reset.
1.5 Function Select Setting (wired R/C only)
Perform the following steps in the operation OFF mode.
Press
,
, and
1
the OFF mode.
In the group control mode, the header unit number is displayed
first.
Each pressing of
2
sequentially.
Choose the main indoor unit (connected to the outdoor unit) this
function is to be performed.
The fan and flap of the selected indoor unit start working.
Specify DN with
3
Set the setting data with
4
Press
Indication on the LCD shows normal operation.
5
• To change the selected indoor unit, go to
• To change the item to be set, go to
Press
to return the operation mode to normal OFF.
6
at the same time for 4 seconds or more in the OFF mode.
indicates indoor unit number in the group sequentially.
buttons.
buttons. (Factory setting: 0000)
at the same time for 4 seconds or more in
indicates indoor unit number in the group
buttons.
buttons.
.
3
Operation
Cooling
Cooling rating
Heating
Heating rating
Auto Cooling
Cooling middle
Auto Cooling
Heating middle
1
Operation procedure
.
2
56
Fan speed
Setting temp.
Quick high
18°C
Quick high
29°C
Auto
23°C
Auto
24°C
above.
3
5
4
6
1
1
2
3
4
Flap position
Horizontal angle
Horizontal angle
Horizontal angle
Horizontal angle
2
END
5
6