Electronic Expansion Valve (Pmv) Control; Pulse Motor Valve (Pmv) Control; Outdoor Fan Control - Toshiba HFCR407C Service Manual

Multi splite type system hfc r407c
Hide thumbs Also See for HFCR407C:
Table of Contents

Advertisement

Item
Operation explanation and applied data, etc.
1a. Electronic
(1) PMV A control (PMV x 2)
expansion
1)
The PMV (pulse motor valve) is controlled between 100 ~ 1000
valve (PMV)
pulses during the operation.
control
2)
The PMV is fully open during the cooling operation
(PMV A1 = 500 pulses, PMV A2 = 500 pulses).
3)
During the heating operation, the opening rate is determined by the
temperature which the TS/TD sensor detects and the pressure rate which PS
detects (Super heat control).
4)
The PMV is fully open when the thermostat is off, when the operation is
switched off or when the operation is ceased under abnormal circumstances.
PMV
opening
rate
1b. Pulse motor
(1) PMV B control
valve (PMV)
The purpose of PMV B control is to control the liquid refrigerant bypass by limiting
control
discharge temperature or compressor internal temperature increase.
1)
Opening is controlled with pulses from 0 ~ 500.
2)
PMV opening is controlled with temp. detected by TS/TD sensors.
3)
PMV openings are fully closed during thermostat-OFF, operation stop, and
emergency stop.
2a. Outdoor fan
(1) Cooling fan control
control
1)
In a specified time when cooling operation is activated, the master outdoor unit
controls the outdoor fan speed (no. of fan driving waves) by Pd pressure. The
slave outdoor unit controls the outdoor fan speed with temperature detected by
TE sensor.
Pd pressure
(kgf/cm
*
PD pressure is maintained between 14.5 ~ 18 kgf/cm
The no. of waves can be controlled between 0 wave (STOP) to 16 waves (all waves).
Outline of control
Outdoor unit
1000
PMV A2
550
500
100
PMV A1
50
Min.
Med.
G)
2
22
[+1 wave/20 sec.]
21
From 2 waves to
19
Max. no. of waves
18
Max.
16 waves
17
[Hold]
From 1 wave to
16
Max. no. of waves
15
[-1 wave/20 sec.]
14
In up time: From 0 wave to 1 wave
In down time:
13
From 15 waves to 1 wave
Interval
[0 wave]:180 sec.
12
control
[1 wave]:30 sec.
11
55
Remarks
Max.
[+1 wave/20 sec.]
(Up to 5 waves)
2
G by the cooling fan control.
11