GUIDE SPECIFICATIONS (CONT)
L. Special Features Available:
1. Coil Options:
Base unit with tin plated indoor coil hairpins.
2. Compressor Start Kit (single phase units only
Shall provide additional starting torque for single- -phase
compressors.
3. Thermostat:
To provide for two- -stage heating and one- -stage cooling in
addition manual or automatic changeover and indoor fan
control.
4. Crankcase Heater:
Shall provide anti- -floodback protection for lowload cooling
applications.
5. Economizer:
a. Economizer controls capable of providing free cooling
using outside air.
b. Equipped with low leakage dampers not to exceed 3%
leakage, at 1.0 IN. W.C. pressure differential.
c. Spring return motor shuts off outdoor damper on power
failure.
6. Electric heaters:
a. Electric heater shall be available as a field installed
option.
b. Heater elements shall be open wire type, adequately
supported and insulated with ceramic bushings.
E2011 Payne Heating & Cooling Systems D
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7310 W. Morris St. D Indianapolis, IN 46231
c. Electric heater packages must provide single point
power connection capability.
7. Filter Rack Kit:
Shall provide filter mounting for downflow applications.
8. Flat Roof Curb:
Curbs shall have seal strip and a wood nailer for flashing
and shall be installed per manufacturer's instructions.
9. Low Ambient Package:
Shall consist of a solid- -state control and outdoor coil tem-
perature sensor for controlling outdoor- -fan motor opera-
tion, which shall allow unit to operate down to 0_F
(- -17.7_C) outdoor ambient temperature.
10. Louvered Grille:
Wire grille shall be standard on all units. Louvered grille
shall be available as a field- -installed option to provide hail
guard and vandalism protection.
11. Manual Outdoor Air Damper:
Package shall consist of damper, birdscreen, and rainhood
which can be preset to admit outdoor air for year- -round
ventilation.
12. Square- -To- -Round Duct Transitions (24- -48 size):
Shall have the ability to convert the supply and return open-
ings from rectangular to round.
Printed in U.S.A.
Edition Date: 02/11
32
Catalog No: SS---PH3G ---03
Replaces: SS--- PH3G--- 01