Toshiba RAV-SM563UT-E Service Manual page 69

Split type
Hide thumbs Also See for RAV-SM563UT-E:
Table of Contents

Advertisement

Toshiba SDI / DI tuotteiden jälleenmyyjä pääkaupunkiseudulla on Jäähdytinpalvelu RefGroup Oy
No.
Item
17
Max. frequency
1) This control is operated by selecting [AUTO] operation
cut control
2) COOL operation mode: the frequency is controlled
3) HEAT operation mode: the frequency is controlled
18
DC motor
1) When the fan operation has started, positioning of the
2) The motor operates according to the command from the
NOTES :
• When the fan rotates while the air conditioner stops due to
entering of outside air, etc, the air conditioner may oper-
ated while the fan motor stops.
• When a fan locking is found, the air conditioner stops, and
an error is displayed.
Outline of specifications
mode.
according to the following figure if To < 28°C.
Ta(˚C) Normal control
+4
+3
Tsc
according to the following figure if To > 15°C.
It cannot be operated on the remote controller at indoor
unit side. (Stop status is held.)
Ta(˚C)
Tsh
–3
–4
Normal control
stator and the rotor are performed.
(Moves slightly with tap sound)
indoor controller.
www.ilmalämpöpumput.com
Max. frequency is restricted
to approximately the rated
cooling frequency
Max. frequency is restricted
to approximately the rated
heating frequency
– 69 –
Remarks
Check code [P12]