Toshiba RAS-M10UKV-E3 Service Manual page 107

Split type
Table of Contents

Advertisement

No.
Part name
Replacement of tempera-
ture sensor for servicing
only
Common service parts of
sensor TO, TS, TE, TGa,
TGb, TGc, TGd
(without TD)
These are parts for
servicing sensors.
Please check that the
accessories shown in the
right table are packed.
Procedure
1) Cut the sensor 100 mm longer than old
one.
2) Cut the protective tube after pulling out
it (200 mm).
3) Move the protective tube toward the
thermal sensor side and tear the tip of
lead wire in two then strip the covering
part.
4) Pass the stripped part through the
thermal constringent tube.
5) Cut the old sensor 100 mm length on
the connector side, and recycle that
connector.
6) Tear the lead wire in two on the connec-
tor side and strip the covering part.
7) Twist the leads on the connector and
sensor sides, and solder them.
8) Move the thermal constringent tubes
toward the soldered parts and heat
them with the dryer and constring them.
9) Wind the attached color tape round the
both terminals of the protective tube
when colored protective tube is used.
10)Fix the sensor again.
NOTES :
1) Store the joint part of the sensor and
the connector in the electric parts box.
2) Never joint them near the thermal
sensor part. Otherwise it would cause
insulation inferiority because of dew
drops.
3) When replacing the sensor using the
colored protective tube, wind the color
tape matching the color of that tube.
Parts name
1
Sensor
2
Sensor Spring (A)
3
Sensor Spring (B)
4
Thermal constringent tube
5
Color tape
6
Terminal
– 107 –
Remarks
Thermal
Connector
sensor part
200
Thermal
constringent tube
Cutting here
100
Soldered part
Dryer
Winding the color tape
Q'ty
Remarks
1
Length : 3m
1
For spare
1
For spare
3
Including one spare
1
9 colors
3
Cutting here
100
Cutting here

Hide quick links: