Gas Connection - Paloma PRS-150N Owner's Manual And Installation Instructions

Room sealed gas space heaters
Table of Contents

Advertisement

All gas work must be carried out by a qualified person and in accordance with the Australian Gas Installations
Standard AS 5601 or AS/NZS 5601.1, and local authority requirements.
CONNECTION SIZES
Model
Gas Connection Size
GAS INLET
The pipe work must be cleared of foreign matter before connection and
purged at the heater gas isolator before attempting to light the heater. If this
procedure is not performed, an ignition failure (code 11) may result on initial
start up.
An isolation valve and disconnection union must be installed to allow servicing
and removal of the heater. Refer to AS/NZS 5601 or AS/NZS 5601.1 for the
correct pipe sizing.
Warning: Before pressure testing the gas supply system always isolate
and disconnect the heater after the isolating valve to prevent the risk of
serious damage to the heater. Warranty does not cover damage of any nature
resulting from failure to observe this precaution. Refer to the heaters rating
label for gas types and pressures.
The heater gas connection must be leak tested before operating the heater.
Test the heater gas connection for leaks using soapy water. DO NOT USE A
NAKED FLAME.

GAS CONNECTION

PRS-150
R½/15
18
PRS-250 & PRS250C
R½/15

Hide quick links: