Samsung RC090MHXEA Installation And Maintenance Manual

Samsung RC090MHXEA Installation And Maintenance Manual

Air source heat pump
Hide thumbs Also See for RC090MHXEA:

Advertisement

Air Source Heat Pump
Installation and Maintenance Manual
Model Numbers:
RC090MHXEA
RC160MHXEA
August 2013
www.samsungehs.co.uk
Hendra – August 2013
1

Advertisement

Table of Contents
loading

Summary of Contents for Samsung RC090MHXEA

  • Page 1 Air Source Heat Pump Installation and Maintenance Manual Model Numbers: RC090MHXEA RC160MHXEA August 2013 www.samsungehs.co.uk Hendra – August 2013...
  • Page 2: The Outdoor Unit (Boiler)

    The outdoor unit (boiler) Deciding on Where to Install the Outdoor Unit The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling circuit and seriously damage the unit. Choose a location where the noise of the Air to Water Heat Pump when running and the discharged air do not disturb any neighbours.
  • Page 3 Pipework Schematic size 9 units The 9kW unit has 1 inch BSP male connections; these should be connected to flexi hoses. To maintain flow rate we recommend 28mm pipework is used with this machine. NEVER use 22mm plastic tube, if you insist on using plastic use 28mm throughout All Pipework including the flexis...
  • Page 4 Pipework Schematic size 16 units The 16 kW unit has 1 inch BSP male connections, these should be connected to flexi hoses (supplied). To maintain flow rate we recommend 28mm pipework is used with this machine. NEVER use 22mm plastic tube, if you insist on using plastic use 28mm throughout All Pipework including the flexis...
  • Page 5 Buffer vessels We don’t normally use buffer vessels on Samsung EHS systems; as long as the water volume circulating is over 20 Litre. The inbuilt variable speed compressor means the unit can operate without a buffer.
  • Page 6 2 port valve and cylinder stat. The valve can be installed in the flow as per the diagram. However as the refrigerant used in the Samsung EHS is R410A it is not able to physically heat above its critical temperature of 72.8C.
  • Page 7 Wiring diagram for heating and HW heat pump: If normally open valves are used connect the live feed for the valves to B10 for HW, B13 for zone 1 and B17 for zone 2 www.samsungehs.co.uk Hendra – August 2013...
  • Page 8: Wiring And Power Supply Information

    Wiring and Power Supply Information: Power The EHS system needs 2 power supplies: One connects into the outdoor unit, 20 Amp for the 9kW and 32 Amp for the size 16 The one for the control box is 16 Amp and wires into the top of the breaker (mcb) in the box Immersion Heater The immersion heater is connected into the control box terminals...
  • Page 9 Using multiple heating zones: When multi zone systems are required the wiring and pipework needs to be set up as below. www.samsungehs.co.uk Hendra – August 2013...
  • Page 10: Start-Up Procedure

    Start Up Procedure: With the power OFF, remove the front of the remote controller, slide it upwards, turn it over DON’T TOUCH THE PCB, there are 8 dip switches near the red sensor, using a small screwdriver flick dip switch 1 and 5 to on. Cooling will no longer be available. Put the controller back on the wall.
  • Page 11: Electrically Testing The Unit

    Electrically testing the unit: It is possible to test each component one after another using a service function. You can use this to make sure you have wired everything correctly. To access service mode press blue set button test button together for 6 seconds. The controller will display TEST.
  • Page 12 Starting it up in heating mode: If you have two port valves you should find the heating valves are open and the hot water valve closed. If you have a 3 port valve it should be open to heating mode. Check that the correct (heating valve is open and the hot water is closed, if it’s wrong check your wiring) Start the unit my Pressing heating on off button (top left...
  • Page 13 What the symbols mean: Setting the correct time www.samsungehs.co.uk Hendra – August 2013...
  • Page 14 Telling the unit it has a cylinder. When the unit is delivered it doesn’t think there is a hot water cylinder cylinder installed. You have to tell the unit about the cylinder. Press test button for 3 seconds The screen will start to flash, Press up twice, 30 will appear Press set (grey) 3011 will appear Press set (grey), 0 will appear Press up once 1 will appear...
  • Page 15: Setting Up The Cylinder Immersion Heater

    Run test in hot water mode In hot water mode check that the 3 port valve or the 2 x 2 ports are sending water into the hot water cylinder, if not check the wiring. Using the view button (blue) on the remote controller check the hot water cylinder temperature and note it down, the hot water temperature is displayed when the tap symbol shows.
  • Page 16: Field Settings

    PCB until you finish setting and exit. Field settings to set see user manual for a full list 1061 length of time backlight is on in the Samsung remote control 2011 low ambient setting for optimisation set to -5 in Scotland...
  • Page 17 When you make a run signal a sun will appear in the screen of the RC, the pump will also start. When an external stat or run signal is used most of the functions of the Samsung remote are disabled. A waging finger shows at the bottom to show this.
  • Page 18 Samsung EHS Warranty Unit 2 Warrior Park Eagle Close Chandlers Ford SO534NF Web site www.samsungehs.co.uk Email sales@samsungehs.co.uk Warranty Registration Card Please complete both sides of this warranty card and return it to activate the warranty Installer Name and Address Installation Address telephone number &...
  • Page 19 The Samsung EHS warranty covers parts with a pre-set labour allowance only. The standard warranty is valid for 12 months from date of commissioning as entered on this card. If the unit is installed by a Samsung approved installer the warranty is automatically extended to 36 months.
  • Page 20: Maintenance Procedure

    Test the concentration of the Anti-freeze (glycol) in the system using a Glycol tester the level should be 25%. If you don’t have a glycol tester a Samsung glycol tester can be bought from your heat pump supplier or online.
  • Page 21: Hot Water

    Leave this page with the Homeowner Your Samsung heat pump heats the house and hot water cylinder much like a normal fossil fuel boiler however there are a couple of differences which you should notice. The radiator temperatures are lower than normal and will alter as the outdoor temperature changes.