Check The Following; Checking Temperature Sensors - Weil-McLain Ultra Commercial Installation And Start-Up Manual

Commercial gas-fired water boiler
Hide thumbs Also See for Ultra Commercial:
Table of Contents

Advertisement

COMMERCIAL GAS
Troubleshooting

Check the following:

1.
Make sure thermostat is calling for heat and con-
tacts (including appropriate zone controls) are
closed. Check for 24 VAC between thermostat wire
nuts and ground.
2.
Make sure all external limit controls are either
installed (and closed) or temporarily jumpered
for testing.
3.
Make sure that connectors to control module are
securely plugged in at module and originating
control.
4.
Gas pressures as specified on
or page 50 (propane).
Always check control module fuses
1.
Turn OFF power to boiler at external line switch.
2.
Remove jacket door and jacket top panel. Rotate
the swing-away control panel forward to expose the
U-Control module and Expansion module.
3.
Remove and inspect the two U-Control fuses and
the Expansion module fuse (located as shown
below).
4.
If necessary, replace the fuse:
a.
Low voltage circuit fuses on U-Control and
Expansion module are 3-amp fast-blow
(Littelfuse 326012P).
84
-
FIRED WATER BOILER
(continued)
page 50 (natural gas)
ALWAYS check control module fuses
before replacing control module or any
major components (blower, etc.). If one
of these fuses is blown, it can prevent
control module or other components
from operating.
— Boiler Manual
b.
Line voltage circuit fuse is 12-amp slow-blow
(Littelfuse 257003).
Do not jumper fuse or replace with any
fuse except as specified. Failure to comply
could result in severe personal injury,
death or substantial property damage.
5.
Reinstall jacket top panel and boiler jacket door
after checking the fuses.
6.
Restore power to boiler at external line switch and
verify boiler operation after completing boiler
service.

Checking temperature sensors

1.
The boiler temperature sensors (flue, outdoor,
boiler out, boiler in, heat exchanger and system)
are all resistance-type devices.
2. Figure 78 shows the correct value for the sensor at
various temperatures.
3.
Use the resistance values at 32°F, 60°F, 70°F and
212°F to measure the sensor resistance at known
temperatures (freezing point, room temperature
and sea level boiling point). For freezing point
and boiling point, insert the sensor in water at that
temperature. Use an ohmmeter to read resistance
value.
4.
To check whether the control module is correctly
sensing temperature, you can use a resistance de-
cade box. Connect the decade box temporarily in
place of a sensor and read the corresponding tem-
perature on the U-Control display. The temperature
should be close to the value corresponding to the
input resistance.
Sensor resistance values
Sensor resistance values
Sensor ohms
Temp
(°F)
Min
32
34265
40
27834
50
21630
60
70
13372
80
90
8504
100
6847
110
5545
Sensor ohms
Temp
(°F)
Max
Min
37871
120
4517
30764
130
4088
140
3043
3364
18727
150
2517
2782
14780
160
2311
11747
170
1744
180
1461
1615
7568
190
200
1038
1147