Advanced Setup - Weil-McLain Ultra Commercial Installation And Start-Up Manual

Commercial gas-fired water boiler
Hide thumbs Also See for Ultra Commercial:
Table of Contents

Advertisement

COMMERCIAL GAS
U-Control operation and setup
U-Control system types and preset parameters
8-character
Fan-coil
FAN-COIL
Finned tube baseboard
FIN BASE
Cast iron baseboard
IRN BASE
Cast iron radiators
RADIATOR
Radiant – slab on grade
RAD SLAB
Radiant – thin slab
RAD SLAB
Radiant – below floor
RADFLOOR
Radiant – above floor
RADFLOOR
Custom
CUSTOM
DHW – system
DOMESTIC
DHW – direct
DOMESTIC
Typical outdoor reset curves
3.
many degrees below target temperature for the boiler to come
on.
4.
perature increases above the target temperature, the boiler firing
rate is reduced. At this many degrees above the target temperature,
the boiler shuts down.
62
-
FIRED WATER BOILER
3-char
Max Target
Outdoor Temp
Temp
for Max Target
FCL
FTB
180
CIB
180
CIR
180
RSG
120
RTS
140
RSU
160
RAF
140
CUS
DHW
DHW
— The temperature must drop this
— While the boiler is firing, as the tem-
— Boiler Manual
(continued)
Min Target
Outdoor Temp
Temp
for Min Target
0
140
70
0
130
70
0
120
70
0
120
70
0
80
70
0
80
70
0
70
0
70
0
70
70
DHW heating ignores
outdoor reset and
warm weather shutdown
ADVANCED SETUP —
Circulator exercising
1.
For each circulator, select whether you want the U-
Control to automatically start the circulator and run for
10 seconds for each 72-hour period of inactivity.
ADVANCED SETUP —
Freeze protection circulators
1.
This function automatically fires the boiler at low fire
and starts the circulators chosen if the heat exchanger
sensor detects a temperature less than 40 °F. The circu-
lators and boiler turn off when the temperature rises
above 45 °F.
ADVANCED SETUP —
Maintenance info
1.
Use this section to enter contractor's information and to
enter an automatic notice for maintenance (default is 12
months). Because this shows on the display, it is an au-
tomatic means of notifying the homeowner of the need
for scheduled maintenance by the technician. Update the
screen reminder to reset for the next maintenance date
after completing required maintenance.
ture sensors.
sensors.
Part number 550-100-086/0809
-