Carrier 58CTA Installation, Start-Up, Operating And Service And Maintenance Instructions page 19

2-stage deluxe, induced combustion 4-way multipoise gas furnace series 140/e
Table of Contents

Advertisement

Gas piping must be installed in accordance with national and
local codes. Refer to current edition of NFGC in the U.S.
Table 6 – Maximum Capacity of Pipe
NOMINAL
INTERNAL
IRON PIPE
DIA.
SIZE
10
IN. (MM)
IN. (MM)
(3.0)
0.622
1/2 (12.7)
175
(158)
0.824
3/4 (19.0)
360
(20.9)
1.049
1( 25.4)
680
(26.6)
1-1/4
1.380
1400
(35.0)
(31.8)
1-1/2
1.610
2100
(38.1)
(40.9)
* Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14 ---In. W.C.)
or less and a pressure drop of 0.5 ---In. W.C. (based on a 0.60 specific
gravity gas). Ref: Table 6 and NFPA54/ANSI Z223.1 ---2012.
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
NOTE: In the state of Massachusetts:
1. Gas supply connections MUST be performed by a li-
censed plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 inches (915 mm).
3. When lever handle type manual equipment shutoff valves
are used, they shall be T- -handle valves.
4. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
Refer to Table 6 for recommended gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. (1.8 M). Joint compound (pipe dope) should be
applied sparingly and only to male threads of joints. Pipe dope
must be resistant to the action of propane gas.
WARNING
!
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death, and/or property damage.
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a
connector which has previously served another gas
appliance. Black iron pipe shall be installed at the furnace
gas control valve and extend a minimum of 2 in. (51 mm)
outside the furnace.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to
avoid damaging gas controls and burner misalignment.
LENGTH OF PIPE --- FT. (M)
20
30
40
50
(6.0)
(9.1)
(12.1)
(15.2)
120
97
82
73
250
200
170
151
465
375
320
285
950
770
660
580
1460
1180
990
900
An accessible manual equipment shutoff valve MUST be
installed external to furnace casing and within 6 ft. of furnace. A
1/8- -in. (3 mm) NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas
supply connection to furnace and downstream of manual
equipment shutoff valve.
NOTE:
The furnace gas control valve inlet pressure tap
connection is suitable to use as test gauge connection providing
test pressure DOES NOT exceed maximum 0.5 psig (14- -In.
W.C.) stated on gas control valve. (See Fig. 48.) Some
installations require gas entry on right side of furnace (as viewed
in upflow). (See Fig. 21.)
2" (51mm)
Street Elbow
Fig. 21 - - Burner and Manifold
Install a sediment trap in riser leading to furnace as shown in Fig.
22. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of furnace gas controls. Place a ground
joint union between furnace gas control valve manifold and
exterior manual equipment gas shutoff valve.
GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
Fig. 22 - - Typical Gas Pipe Arrangement
19
A08551
A02035