UNIT
ELECTRICAL
50HX
CHARACTERISTICS
036
208/230-1-60, 208/230-3-60, 460-3-60
042
208/230-1-60, 208/230-3-60, 460-3-60
048
208/230-1-60, 208/230-3-60
060
208/230-1-60, 208/230-3-60
CENTER OF GRAVITY (in./mm)
UNIT
50HX
X
Y
036
21.05/535.0 20.53/521.0 16.47/418.0
042
21.05/535.0 20.53/521.0 16.47/418.0
048
19.62/498.3 20.61/523.5 17.31/439.7
060
19.58/497.3 20.64/524.3 17.31/439.7
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-fan discharge.
2.
Indicates center of gravity.
3. Dimensions in ( ) are in mm.
SIZES 024-030 WITH OPTIONAL BASE RAIL
UNIT WEIGHT
lb
kg
336
153
51/23
336
153
51/23
379
172
94/43
393
179
97/44
NEC REQ'D CLEARANCES — in. (mm)
Between Units, Control Box Side . . . . . . . 42 (1066.8)
Z
Unit and Ungrounded Surfaces,
Control Box Side . . . . . . . . . . . . . . . . 36 (914.4)
Unit and Block or Concrete Walls and
Other Grounded Surfaces,
Control Box Side . . . . . . . . . . . . . . . . 42 (1066.8)
CORNER WEIGHT (lb/kg)
A
B
C
D
108/49
86/39
91/41
108/49
86/39
91/41
86/39
118/54
81/37
90/41
121/55
85/39
REQ'D CLEARANCES FOR SERVICING
— in. (mm)
Indoor Coil Access Side . . . . . . 30 (762.0)
Control Box Access Side
. . . . . 30 (762.0)
(Except for NEC Requirements)
Unit Top . . . . . . . . . . . . . . . . 36 (914.4)
Side Opposite Ducts . . . . . . . . 30 (762.0)
REQ'D CLEARANCES TO COMBUSTIBLE
MAT'Ll — in. (mm)
Unit Top
. . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . 0
Bottom of Unit . . . . . . . . . . . . . . . . . . 0
Vertical Discharge First 12 inches
(304.8 mm) of Supply Duct . . . . 1 (25.4)
LEGEND
K.O.
— Knock Out
MAT'L — Material
NEC
— National
Electrical Code