Features/Benefits (cont)
All units are designed with a single
continuous top piece to eliminate
any possible leaking at the seams
or gasketing, which tends to deter-
iorate over time and shift during
rigging procedures.
Low-voltage wiring connections
are easily made due to the termi-
nal board which is conveniently
located for quick simple access.
Field-installed accessory electric
heaters are available in a wide range

Model number nomenclature

ARI* capacities
UNIT
NOMINAL
STANDARD
50HX
TONS
CFM
024
2
800
030
2
1000
1
2
036
3
1200
042
3
1400
1
2
048
4
1600
060
5
1800
LEGEND
Bels
— Sound Levels (1 bel = 10 decibels)
COP
— Coefficient of Performance
DOE
— Department of Energy
HSPF — Heating Seasonal Performance Factor
SEER — Seasonal Energy Efficiency Ratio
*Air Conditioning & Refrigeration Institute.
†Rated in accordance with ARI Standard 210/240, latest revision and/or U.S. Government DOE test procedures.
**Rated in accordance with ARI Standard 270, latest revision.
of capacities. Single-point wiring kit
makes installation simple.
Downflow-only option is shipped
from factory for vertical ductwork con-
nection and requires no conversion.
Optional base rail provides holes
for rigging and forklifts as well as
an elevated mounting frame that gives
additional structural support to hori-
zontal installations.
COOLING AND HEATING CAPACITIES AND EFFICIENCIES
NET COOLING†
NET HEATING†
CAPACITIES
SEER†
AT 95 F (Btuh)
At 47 F (Btuh)
23,400
12.0
28,600
12.0
35,000
12.0
41,500
12.0
47,500
12.0
57,000
11.0
NET HEATING†
COP†
CAPACITIES
CAPACITIES
At 47 F
(Btuh)
23,800
3.2
28,200
3.2
33,000
3.2
40,000
3.3
44,000
3.5
57,000
3.5
Serviceability
Standardized components are
found in all safety devices, outdoor-fan
motors, and control boards. This
allows for greater inventory control,
familiarity, and fewer stocked parts.
Easily accessible refrigerant
access ports on all discharge, suc-
tion, and liquid lines permit easy and
accurate measurements.
COP†
At 17 F
HSPF
At 17 F
(Btuh)
(Btuh)
12,400
1.8
6.9
15,400
1.9
7.1
18,000
1.9
7.0
21,000
1.9
7.0
23,600
2.0
7.0
31,800
2.0
7.2
SOUND
RATINGS**
(Bels)
7.8
7.8
8.0
8.0
8.2
8.2
3