Carrier 50HX024-060 Product Data page 8

High efficiency single-package 2 to 5 nominal tons
Table of Contents

Advertisement

Dimensions (cont)
UNIT
ELECTRICAL
50HX
CHARACTERISTICS
036
208/230-1-60, 208/230-3-60, 460-3-60
042
208/230-1-60, 208/230-3-60, 460-3-60
048
208/230-1-60, 208/230-3-60
060
208/230-1-60, 208/230-3-60
CENTER OF GRAVITY (in./mm)
UNIT
50HX
X
Y
036
21.23/539 20.46/520 13.65/347
042
21.23/539 20.46/520 13.65/347
048
19.70/500 20.54/522 15.00/381
060
19.65/499 20.59/523 15.00/381
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2.
Indicates center of gravity.
3. Dimensions in ( ) are in mm.
8
SIZES 036-060 WITHOUT BASE RAIL
UNIT WEIGHT
lb
kg
316
144
316
144
359
163
373
170
NEC REQ'D CLEARANCES — in. (mm)
Between Units, Control Box Side . . . . . . . . . . . . . 42 (1066.8)
Z
Unit and Ungrounded Surfaces, Control Box Side . . . . 36 (914.4)
Unit and Block or Concrete Walls and Other
Grounded Surfaces, Control Box Side . . . . . . . . . 42 (1066.8)
CORNER WT (lb/kg)
A
B
C
D
46/21
103/47
81/37
86/39
46/21
103/47
81/37
86/39
89/40
81/37
113/51
76/35
92/42
85/39
116/53
80/36
REQ'D CLEARANCES FOR SERVICING
— in. (mm)
Indoor Coil Access Side . . . . . . 30 (762.0)
Control Box Access Side
. . . . . 30 (762.0)
(Except for NEC Requirements)
Unit Top . . . . . . . . . . . . . . . . 36 (914.4)
Side Opposite Ducts . . . . . . . . 30 (762.0)
REQ'D CLEARANCES TO COMBUSTIBLE
MAT'L — in. (mm)
Unit Top
. . . . . . . . . . . . . . . . . . . . . 0
Duct Side of Unit . . . . . . . . . . . . . . . . 0
Side Opposite Ducts . . . . . . . . . . . . . . 0
Bottom of Unit . . . . . . . . . . . . . . . . . . 0
Vertical Discharge First 12 in.
(304.8 mm) of Supply Duct . . . . 1 (25.4)
LEGEND
K.O.
— Knock Out
MAT'L — Material
NEC
— National
Electrical Code

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50hx02450hx03050hx03650hx04250hx04850hx060

Table of Contents