Outdoor units may be connected to indoor section using
accessory tubing package or field- -supplied refrigerant grade
tubing of correct size and condition. For tubing requirements
beyond 80 ft, substantial capacity and performance losses can
occur. Following the recommendations in the Application
Guideline and Service Manual- -Residential Split- -System Air
Conditioners and Heat Pumps will reduce these losses. Refer to
Table 1 for accessory requirements. Refer to Table 2 for field
tubing diameters.
There are no buried- -line applications greater than 36 in.
If refrigerant tubes or indoor coil are exposed to atmosphere, they
must be evacuated to 500 microns to eliminate contamination and
moisture in the system.
OUTDOOR UNIT CONNECTED TO FACTORY
APPROVED INDOOR UNIT
Outdoor unit contains correct system refrigerant charge for
operation with approved ARI rated indoor unit when connected
by 15 ft of field- -supplied or factory- -accessory tubing, and
factory supplied filter drier. Check refrigerant charge for
maximum efficiency.
Refrigerant Tubing and Sweat Connections
Connect vapor tube to fitting on outdoor unit vapor service
valves (see Table 2). Connect liquid tubing to adapter tube on
liquid service valve. Use refrigerant grade tubing.
Remove plastic retainer holding outdoor piston in liquid service
valve, leaving the piston and piston retainer inside the valve.
Connect sweat/flare adapter provided, to valve. (See Fig. 6.)
Connect refrigerant tubing to fittings on outdoor unit vapor and
liquid service valves. Service valves are closed from factory and
ready for brazing. After wrapping service valve with a wet cloth,
tubing set can be brazed to service valve using either silver
bearing or non- -silver bearing brazing material. Do not use soft
solder (materials which melt below 800°F). Consult local code
requirements. Refrigerant tubing and indoor coil are now ready
for leak testing. This check should include all field and factory
joints.
PISTON BODY
SWEAT/FLARE ADAPTER
Fig. 6 --- Liquid Service Valve
5
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service valves must be wrapped in a heat- -sinking
material such as a wet cloth while brazing.