Application data (cont)
ANTIFREEZE
ANTIFREEZE %
TYPE
Water
0
5
Propylene
15
Glycol
25
5
Methanol
15
25
5
Ethanol
15
25
5
Ethylene
15
Glycol
25

Electrical data

50PEC
VOLTAGE
V-PH-Hz
UNIT SIZE
CODE
A
115-60-1
09
G
208/230-60-1
E
265-60-1
A
115-60-1
12
G
208/230-60-1
E
265-60-1
G
208/230-60-1
15
E
265-60-1
G
208/230-60-1
18
E
265-60-1
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA
— Locked Rotor Amps
RLA
— Rated Load Amps
30
ANTIFREEZE CORRECTION TABLE
COOLING
EWT 90 F
Sensible
Total Capacity
Capacity
1.000
1.000
0.995
0.995
0.986
0.986
0.978
0.978
0.997
0.997
0.990
0.990
0.982
0.982
0.998
0.998
0.994
0.994
0.986
0.986
0.998
0.998
0.994
0.994
0.988
0.988
COMPRESSOR
MIN/MAX
VOLTAGE
QTY
RLA
104/126
1
197/254
1
239/292
1
104/126
1
197/254
1
239/292
1
197/254
1
239/292
1
197/254
1
239/292
1
Power
Htg Capcity
1.000
1.000
1.003
0.989
1.009
0.968
1.014
0.947
1.002
0.989
1.007
0.968
1.012
0.949
1.002
0.981
1.005
0.944
1.009
0.917
1.002
0.993
1.004
0.980
1.008
0.966
FAN MOTOR
FLA
LRA
8.1
46.5
0.6
4.5
23.0
0.4
3.1
24.0
0.4
10.6
55.8
1.0
5.2
24.0
0.6
4.2
25.0
0.4
6.1
30.0
0.8
4.7
28.5
0.6
6.8
38.0
0.7
6.2
29.0
0.6
HEATING
EWT 30 F
CORRECTION
Power
EWT 30 F
1.000
0.997
0.990
0.983
0.997
0.990
0.984
0.994
0.983
0.974
0.998
0.994
0.990
TOTAL UNIT
MIN CIRCUIT
FLA
AMPS
8.6
10.7
4.9
6.0
3.5
4.3
11.6
14.3
5.8
7.1
4.6
5.7
6.9
8.4
5.3
6.5
7.5
9.2
6.8
8.4
WPD
FACTOR
1.000
1.070
1.210
1.360
1.070
1.160
1.220
1.140
1.300
1.360
1.040
1.120
1.200
MAX FUSE/
HACR
15
15
15
25
15
15
15
15
15
15

Advertisement