Carrier Aquazone 50PEC09-18 Installation, Start-Up And Service Instructions Manual

Carrier Aquazone 50PEC09-18 Installation, Start-Up And Service Instructions Manual

Water source heat pumps console unit with puron refrigerant (r-410a)

Advertisement

Quick Links

Installation, Start-Up and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 1 - Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 - Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 3 - Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Step 4 - Make Electrical Connections . . . . . . . . . . . 4
Hose Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 6 - Install Condensate Piping . . . . . . . . . . . . 10
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
System Cleaning and Flushing . . . . . . . . . . . . . . . . 10
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . 13
Exchanger Well Systems . . . . . . . . . . . . . . . . . . . 13
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Cooling Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Heating Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DELUXE D PACKAGES . . . . . . . . . . . . . . . . . . . . 17
UPM Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
UNIT-MOUNTED CONTROLLER . . . . . . . . . . . . . . . 21
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 23
START-UP CHECKLIST . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before start-
ing installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500267-01
Page
Printed in U.S.A.
Form 50PEC-5SI Rev. A
Water Source Heat Pumps Console Unit
with Puron
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the litera-
ture, tags and labels attached to the unit, and other safety precau-
tions that may apply.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire, electrical shock or other
conditions which may cause personal injury or property damage.
Consult a qualified installer, service agency, or your distributor for
information or assistance. The qualified installer or service agency
must use factory-authorized kits or accessories when modifying
this product. Refer to the individual instructions packaged with the
kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for brazing operations. Have fire extinguisher
available. Read these instructions thoroughly and follow all warn-
ings or cautions attached to the unit. Consult local building codes
and applicable electrical codes for special installation require-
ments.
Electrical shock can cause personal injury or death. Before in-
stalling or servicing system, always turn off main power to sys-
tem. There may be more than one disconnect switch. Turn off
accessory heater power if applicable.
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and goggles
and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from system
using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen and
the work area should be well ventilated. Refrigerant in
contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter and
remove component from unit. Use a pan to catch any oil
that may come out of the lines and as a gage for how
much oil to add to the system.
e. Carefully un-sweat remaining tubing stubs when neces-
sary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal inju-
ry or death.
Pg 1
Aquazone™
50PEC09-18
Refrigerant (R-410A)
®
WARNING
DANGER
3-2020
Replaces: 50PEC-4SI

Advertisement

Table of Contents
loading

Summary of Contents for Carrier Aquazone 50PEC09-18

  • Page 1: Table Of Contents

    Aquazone™ 50PEC09-18 Water Source Heat Pumps Console Unit with Puron Refrigerant (R-410A) ® Installation, Start-Up and Service Instructions should be performed by trained service personnel. When working CONTENTS on air-conditioning equipment, observe precautions in the litera- Page ture, tags and labels attached to the unit, and other safety precau- SAFETY CONSIDERATIONS .
  • Page 2: General

    CAUTION CAUTION All refrigerant discharged from this unit must be recovered without exception. Technicians must follow industry accepted DO NOT re-use compressor oil or any oil that has been ex- guidelines and all local, regional, and national statutes for the posed to the atmosphere.
  • Page 3 RIGHT HAND WATER LEFT HAND WATER CONNECTIONS CONNECTIONS LEFT HAND WATER CONNECTIONS WATER OUT ELECTRICAL BOX WATER IN CONDENSATE WATER RIGHT HAND WATER CONNECTIONS ELECTRICAL BOX WATER IN WATER OUT CONDENSATE WATER UNIT SIZE Cabinet End Grilled Edge Control Discharge Clearance to Subbase to Return...
  • Page 4: Step 3 - Mount Unit

    Table 1 — 50PEC Physical Data 50PEC UNIT COMPRESSOR (qty 1) Rotary Rotary Rotary Rotary Maximum Water Working Pressure (psig/kPa) 400/3100 400/3100 400/3100 400/3100 STANDARD FAN MOTOR AND BLOWER Fan Motor Type Fan Motor (hp) Blower Wheel Size (Dia x W) (in.) (qty) 5.5 x 8.0 (X 2) 5.5 x 8.0 (X 2) 5.5 x 8.0 (X 2)
  • Page 5 Table 2 — Electrical Data — 50PEC Units With or Without Disconnect 50PEC COMPRESSOR BLOWER VOLTAGE UNIT CIRCUIT FUSE/ V-PH-Hz SIZE AMPS HACR 115-1-60 45.6 0.10 10.9 208/230-1-60 22.2 0.10 265-1-60 18.8 0.10 115-1-60 58.4 0.25 13.3 208/230-1-60 27.9 0.25 265-1-60 22.2 0.25...
  • Page 6 UPM STATUS LED - BLINK CODES HIGH PRESSURE FAULT LOW PRESSURE FAULT CONDENSER FREEZE CONDITION CONDENSATE OVERFLOW FAULT BROWN OUT FAULT EVAPORATOR FREEZE CONDITION FAN MOTOR SPEED TABS - 4 POLE MOTORS FAN MOTOR SPEED TABS - 3 POLE MOTORS UNIT CAPPED CAPPED...
  • Page 7 UPM STATUS LED - BLINK CODES HIGH PRESSURE FAULT LOW PRESSURE FAULT CONDENSER FREEZE CONDITION CONDENSATE OVERFLOW FAULT BROWN OUT FAULT EVAPORATOR FREEZE CONDITION FAN MOTOR SPEED TABS - 4 POLE MOTORS FAN MOTOR SPEED TABS - 3 POLE MOTORS UNIT CAPPED CAPPED...
  • Page 8 UNIT TERMINAL BLOCK (TB1) CLASS II VOLTAGE OPTIONAL WIRING STANDARD COMPONENTS: DATS - DISCHARGE AIR TEMP SENSOR LWTS - LEAVING WATER TEMP SENSOR J1-9 USED TO CONNECT FIRE ALARM RELAY OR PHASE MONITOR OPTIONS FACTORY JUMPER IS INSTALLED ON J5-5 AND J5-6 IF CONDENSATE FLOAT SWITCH (NC) IS NOT PRESENT FOR 2-STAGE UNITS, CONNECT CMR CONN ACROSS PINS 4 AND 6 OF CMR1 WITH SIGNAL CMR-4 GOING TO PIN 4 AND SIGNAL CMR-2 GOING TO PIN 6.
  • Page 9 FAN MOTOR SPEED TABS - 3 POLE MOTORS FAN MOTOR SPEED TABS - 4 POLE MOTORS UNIT CAPPED UNIT CAPPED CAPPED Fig. 5 — Wiring Diagram with Unit Mounted Controller...
  • Page 10: Step 5 - Install Supply And Return Piping

    Follow the instructions below to properly clean and flush the sys- tep 5 — Install Supply and Return Piping tem: The following items should be adhered to in addition to applicable Verify that electrical power to the units is disconnected, and piping codes.
  • Page 11: System Checkout

    • Check the electrical fusing and wiring for the correct size. Table 3 — Air and Water Limits CAUTION 50PEC UNIT COOLING (F) HEATING (F) Min Ambient Air Ensure cabinet and electrical box are properly grounded. Fail- Rated Ambient Air ure to follow these procedures may result in damage to equip- Max Ambient Air ment.
  • Page 12 Table 4 — Water Quality Guidelines CLOSED CONDITION HX MATERIAL* OPEN LOOP AND RECIRCULATING WELL** RECIRCULATING† Scaling Potential — Primary Measurement Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below. pH/Calcium pH <...
  • Page 13: Start-Up

    These systems typically use a common loop maintained at 60 to Set the thermostat switch to “HEAT”. 90°F. Carrier recommends using a closed circuit evaporative cool- 10. Increase the thermostat setting approximately 5 degrees ing tower with a secondary heat exchanger between the tower and the water loop.
  • Page 14 Table 5 — Operating Temperatures and Pressures COOLING HEATING UNIT FLOW SUCTION DISCHARGE SUCTION DISCHARGE EWT (F) FLUID TEMP AIR TEMP FLUID TEMP AIR TEMP SIZE (GPM) PRESSURE PRESSURE PRESSURE PRESSURE RISE (F) DROP (F) RISE (F) DROP (F) psig psig psig psig...
  • Page 15: Operation

    OPERATION Table 6 — Water Side Pressure Drop NOTE: See Fig. 6 for sequence of operations. PRESSURE PRESSURE 50PEC UNIT DROP DROP SIZE Cooling Mode (PSIG) (ft wg) Energizing the “O” terminal energizes the unit reversing valve in 0.98 2.25 the cooling mode.
  • Page 16 START RESET ON R RESET ON Y1 = ON R = 24VAC POWER/ SWITCHES/SENSOR CLEAR FAULTS STATUS CHECK BLINK CODE ON STATUS LED SOFT LOCKOUT COUNTER V > 18VAC RECORD ALARM NEEDED? START COUNTER (IF APPLICABLE) CNT = CNT+1 HPC = CLOSED LOCKOUT CAN BE SET COUNT = 2...
  • Page 17: Safety Devices And The Complete C And Deluxe D Packages

    SAFETY DEVICES AND THE COMPLETE C AND Units with Aquazone Complete C Package DELUXE D PACKAGES Units with Complete C package include the following features: Units are provided with a Complete C package that controls the ANTI-SHORT CYCLE TIMER compressor operation and monitors the safety controls that protect A 5-minute delay on break timer prevents compressor short the unit (see Fig.
  • Page 18: Units With Aquazone Deluxe D Package

    TEST DIP SWITCH Table 12 — Complete C DIP Switch Default Position A test dip switch is provided to reduce all time delays settings to 10 seconds during troubleshooting or verification of unit SWITCH OPERATION (Default) operation. LOCKOUT NOTE: Operation of unit in test mode can lead to accelerated wear RESET and premature failure of components.
  • Page 19 MODULATING OA DAMPER WITH DCV FAN SPEED CONTROL — DURING HEATING The control can be configured to operate a modulating ventilation Whenever heat is required and active, the control continuously damper during occupied periods that responds to changing CO monitors the supply air temperature to verify it does not rise above levels from an optional sensor.
  • Page 20 POWER FAIL RESTART DELAY an alarm state, the control will start a timer and after the timer ex- ceeds a configurable 'Condensate Overflow Alarm Delay' limit The control provides a delay when recovering from a power fail- (10 seconds default), the control will generate an alarm and the ure in order to insure stable utility power and to prevent excessive unit will disable the compressor, dehumidification and fan outputs.
  • Page 21: Unit-Mounted Controller

    Fig. 8 — WSHP Open Control Package • Selectable options: UNIT-MOUNTED CONTROLLER - Manual/Automatic changeover Designed to enhance the unit operation with more flexibility, ac- - Fan speed – High or Low curate control and operating modes the unit-mounted controller provides an increased level of comfort in the conditioned space to- - Fan operation constant fan or cycling with compressor gether with solid-state reliability and ease of operation.
  • Page 22: Low Temperature Loop Application

    Locate High Pressure and Freeze Stat mated wires labeled D and C, respectively. Disconnect Yellow wire labeled B from black wire labeled C. Connect yellow wire labeled A to yellow wire labeled D. Leave black wires B and C disconnected from any circuits. This completes the Freeze Stat Bypass Field Rework.
  • Page 23: Troubleshooting

    Periodic lockouts almost always are caused by air or water flow TROUBLESHOOTING problems. The lockout (shutdown) of the unit is a normal protec- Troubleshooting Checks and Correction column in Table 13 may tive measure in the design of the equipment. If continual lockouts reflect a possible fault that may be one of, or a combination of occur, call a technician immediately and have them check for: wa- causes and solutions.
  • Page 26 8-733-954-887 © 2020 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500267-01 Printed in U.S.A. Form 50PEC-5SI Rev. A Pg 26 3-2020 Replaces: 50PEC-4SI...
  • Page 27: Start-Up Checklist

    50PEC UNIT START-UP CHECKLIST NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sec- tions of this Installation, Start-Up and Service document.
  • Page 28 *Look up pressure drop in Table 6 to determine flow rate. †Use 500 for water, 485 for antifreeze. 8-733-954-887 © 2020 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500267-01 Printed in U.S.A.

Table of Contents