Venting System Length Calculations - Bryant LEGACY 912SA Product Data

92.1 afue legacy line single-stage 4-way multipoise condensing gas furnace
Hide thumbs Also See for LEGACY 912SA:
Table of Contents

Advertisement

Venting System Length Calculations

The Total Equivalent Vent Length (TEVL) for EACH combustion air or vent pipe equals the length of the venting system, plus the equivalent
length of elbows used in the venting system from Table 2.
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer's data for equivalent lengths of flexible vent pipe or other termination systems. DO NOT ASSUME that one
foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Tables 1 and 3.
Example 1
A direct- -vent 60,000 Btuh furnace installed at 2100 ft. (640 M). Venting system includes, FOR EACH PIPE, 100 feet (30 M) of vent pipe,
95 feet (28 M) of combustion air inlet pipe, (3) 90_ long radius elbows, (2) 45_ long radius elbows and a factory accessory concentric vent
kit.
Can this application use 2- -in. (50 mm ND) PVC/ABS DWV vent piping?
Measure the required linear length of air inlet and vent pipe; insert the
longest of the two here:
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the
vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the
vent or inlet pipe)
Add equiv length of vent termination
Add correction for flexible vent pipe, if any
Total Equivalent Vent Length (TEVL)
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Example 2
A direct- -vent 60,000 Btuh furnace installed at 2100 ft. (640 M) Venting system includes, FOR EACH PIPE, 100 feet (30 M) of vent pipe,
95 feet (28 M) of combustion air inlet pipe, (3) 90_ long radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6 M)
of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
Assume that one meter of flexible 60 mm or 80 mm polypropylene pipe equals 2 Meters of PVC/ABS pipe. VERIFY FROM VENT
MANUFACTURER'S INSTRUCTIONS.
Can this application use 60 mm (O.D.) polypropylene vent piping? If not what size piping can be used?
Measure the required linear length of air inlet and vent pipe; insert the
longest of the two here:
Add equiv length of (3) 90º long-radius elbows
(use the highest number of elbows for either the
vent or inlet pipe)
Add equiv length of (2) 45º long-radius elbows
(use the highest number of elbows for either the
vent or inlet pipe)
Add equiv length of vent termination
Add correction for flexible vent pipe, if any
Total Equivalent Vent Length (TEVL)
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
Maximum Equivalent Vent Length (MEVL)
Is TEVL less than MEVL?
100 ft
3
x
3 ft
=
9 ft.
2
x
1.5 ft
=
3 ft.
0 ft.
0 ft.
112 ft.
127 ft.
YES
100 ft
3
x
3 ft
=
9 ft.
0
x
=
0 ft.
9 M
x
3 ft/M
=
18 ft.
1.8
x
20 ft
=
36 ft.
163 ft.
127 ft.
NO
250 ft.
YES
8
Use length of the longer of the vent
or air inlet piping system
From Table 2
From Table 2
From Table 2
From Vent Manufacturer's instructions;
zero for PVC/ABS DWV
Add all of the above lines
For 2" pipe from Table 1
Therefore, 2" pipe may be used
Use length of the longer of the vent
or air inlet piping system
From Vent Manufacturer's instructions
From Vent Manufacturer's instructions
From Vent Manufacturer's instructions
From Vent Manufacturer's instructions
Add all of the above lines
For 2" pipe from Table 1
Therefore, 60mm pipe may NOT be used;
try 80 mm
For 3" pipe from Table 1
Therefore, 80 mm pipe may be used