p2016[0...3]
CI: Comm IF USS PZD send word / Comm USS send word
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Selects the PZD (actual values) to be sent via the commissioning interface USS.
The actual values are displayed on an intelligent operator panel (IOP).
Index:
[0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
r2019[0...7]
Comm int error statistics / Comm err
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the receive errors at the commissioning interface (USS, RS232).
Index:
[0] = Number of error-free telegrams
[1] = Number of rejected telegrams
[2] = Number of framing errors
[3] = Number of overrun errors
[4] = Number of parity errors
[5] = Number of starting character errors
[6] = Number of checksum errors
[7] = Number of length errors
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: 4000H
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: U32 / Integer16
Data set: -
Factory setting
0
Data type: Unsigned32
Data set: -
Factory setting
-
1-247